T600HCx-3 Single-Stage Thermostats Installation Instructions

4

  

Setup and Adjustments

Thermostat Operation Overview 

Thermostat User Interface Keys

The T600HCx-3 thermostat user interface consists of 
five keys on the front cover (as illustrated in Figure 7). 
The function of each key is as follows:

Use  the 

YES/SCROLL

 key to:

-

confirm menu selections and to advance to the 
next menu item

-

stop the Status Display Menu from scrolling 
and to manually scroll to the next parameter on 
the menu

Note:

When the thermostat is left unattended for 

45 seconds, the thermostat display resumes scrolling.

Use  the 

NO

 key to decline a parameter change and 

to advance to the next menu item.

Use  the 

MENU

 key to:

-

access the Main User Menu or exit the menu

-

access the Installer Configuration Menu or to 
exit the menu (See the 

Configuring the 

T600HCx-3 Thermostat 

section.)

Use  the 

UP/DOWN

 arrow keys to change the 

configuration parameters and to activate a setpoint 
adjustment.

Backlit Liquid Crystal Display (LCD)

The T600HCx-3 thermostat includes a 2-line, 
8-character backlit display. Low-level backlighting is 
present during normal operation, and it brightens when 
any user interface key is pressed. The backlight returns 
to low level when the thermostat is left unattended for 
45 seconds.

Light-Emitting Diodes (LEDs)

Three LEDs are included to indicate the fan status, call 
for heat, or call for cooling:

The 

FAN

 LED is on when the fan is on.

The 

HEAT

 LED is on when heating is on.

The 

COOL

 LED is on when cooling is on.

Programming Overview

There are three menus used to view, program, and 
configure the T600HCx-3 thermostat:

The 

Status Display Menu

 is displayed during normal 

thermostat operation. This menu continuously scrolls 
through the following parameters:

Room Temperature

Day and Time (T600HCP-3)

System Mode

Occupancy Status – Occupied/Unoccupied/
Override

Outdoor Temperature – An outdoor air temperature 
sensor must be connected.

Applicable Alarms – The backlight lights up as an 
alarm condition is displayed.

Table 1:  Terminal Identification (See Figure 5.)

Number

Label

Function

2

Y1

Energizes on a call for cooling.

3

G

Energizes fan in accordance with 
selected fan mode.

4

RC

24 VAC from equipment transformer

5

C

24 VAC (Common) from equipment 
transformer

6

RH

24 VAC for heating stage

7

W1

Energizes on a call for heating.

10

Aux

Auxiliary output

11

DI1

Configurable Digital Input 1

12

DI2

Configurable Digital Input 2

13

RS

Remote Room Temperature Sensor

14

Scom

Sensor Common

15

OS

Outdoor Air (OA) Sensor

16

MS

Not Used

Figure 7: Front Cover of Thermostat

70.0ºF

Room Temp

YES

NO

Backlit, plain text

LCD is easy to read

in any condition.

Five keys on the thermostat
make operation easy and intuitive.

LEDs indicate
system activity.

F

IG

:T

6

0

0

_

fr

n

t

Содержание T600HCN-3

Страница 1: ...nn es entrantes un quipement dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l quipement c...

Страница 2: ...at mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with t...

Страница 3: ...ion avant de r aliser tout raccordement lectrique afin d viter tout risque de d charge lectrique CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections...

Страница 4: ...conds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan is on The HEAT LED is on when heating is on The COO...

Страница 5: ...he scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each input can be configured to the Selection Options included in Table 2 Table 2 Installer Confi...

Страница 6: ...0 sec Frost pr Provides a minimum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat Default off on Enabled off Disabled Heat max4 Sets the Occupied and Unoc...

Страница 7: ...Main User Menu or DI1 or DI2 configured as a temporary override remote contact RemOVR Sets the effective duration of the Temporary heating or cooling setpoints set using the up down arrow keys defaul...

Страница 8: ...ve recovery is disabled if either DI1 or DI2 is configured as remote NSB Default off on Enabled provides the desired occupied temperature at the start of the occupied schedule off Disabled provides th...

Страница 9: ...DI2 is configured to operate as a remote override contact this menu is disabled To override the unoccupied state while in the Main User Menu 1 Press the NO key to all prompts until the Override Sched...

Страница 10: ...temperature setting menu Press the YES key to change the occupied cooling setpoint Press the NO key to advance to the occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature...

Страница 11: ...ress the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to...

Страница 12: ...menu Press the YES key to set the schedule for Monday or press the NO key to advance to Tuesday Press the YES key to set the occupied start time for Monday or press the NO key to advance to Tuesday S...

Страница 13: ...he UP DOWN arrow keys to set the second unoccupied start time Press the YES key to enter the time Press the YES key to set the schedule for Tuesday or press the NO key to advance to Wednesday Press th...

Страница 14: ...no alarm or backlight should be present If the day or time is incorrect repeat the Setting the Day and Time procedure Setting Schedule Hold The schedule hold menu is used to set a permanent hold on t...

Страница 15: ...hermostat fails to operate within its specifications replace the unit For a replacement thermostat contact the nearest Johnson Controls representative Table 8 Accessories Order Separately Code Number...

Страница 16: ...5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C bet...