P/N 24-85784-119 Rev. - Issue Date 11 2012
T5000-E
English
Instructions
•
On/off:
press
to turn on, press again to turn off, close the fan and valve.
•
Setting temperature:
Press either
or
buttons to increase or decrease the setpoint by 0.5 °C.
•
Mode selection:
press
to change the working mode,
cooling,
heating,
ventilating (no heat mode for T5200-TC-9JS0)
•
Fan speed selection:
press
to choose the speed
(hi),
(med),
(low),
(auto).
Under “AUTO” mode, the fan-speed will be changed automatically. Auto LOW-speed when the difference between room
temperature and set-point exceed 1 °C, Auto MED-speed when exceed 2 °C, Auto HI-speed when exceed 3 °C.
•
Valve Control:
under cool (heat) mode, the valve will be open while the difference between room temperature and setpoint
exceed 1 °C; while the room temperature reaches setpoint, the valve is closed with the fan still running.
Time-On and Time-Off Operation
• Hold down the
button for 3 seconds will enter the Timer On-Off setting. When the
,
and
appear, press
and
keys to set the duration of the time delay for automatic switch ON.
Press
button again,
,
and
appear, press
and
keys to set the duration of the time delay for automatic switch
OFF. Set time duration to
, to cancel the setting.
After one cycle for Time-on and Time-off the setting will be automatically canceled.
Lock function
•
Lock function:
The thermostat will be locked automatically after 0 seconds under the lock function. Hold down the fan key 5
seconds to unlock.
Unoccupied energy-saving mode
(T5200-TB-9JS0)
• Unoccupied energy-saving mode (by entrance card): While entrance card is pulled out, the temperature automatically set to
26 °C, fan is on LO-speed if the thermostat is in cool mode; the temperature set to 18 °C, fan is on LO-speed if in heat mode.
Low Temperature protection setting
• On power Off status and when room temperature is lower than 5 °C, heat function will be automatically switched on,
appears,
the fan is set to HI-speed and the valve (heat valve for T5200-TF-9JS0) is opened. When the room temperature reaches 7 °C, the
setting will be automatically canceled.
• On power Off status, press
and keep 5 seconds, display
or
, press
,
to adjust the parameter.
means
cancelling low temperature protection,
means the protection function is on. Factory setting is
.
Temperature setting
If customers hope the displayed temperature higher or lower than the real temperature, operate as follows:
• On power off status, press both
and
, keep 5 seconds, display
(no working mode display), press
or
adjust
the temperature, auto-confirmed after 6 seconds.
Alarm
• When the sensor is in fault, thermostat will close the fan and valve, display
,
and
.
: Sensor short cut alarm
: Sensor circuit breaker alarm
Display
, temperature > 55 °C; display
, temperature < 0 °C
Functional Code Setting Table (only when Thermostat is OFF)
•
Enable the setting table:
hold down the
and
for 5 seconds,
01
and code appeare, after which press
button to select
code, use
and
buttons to adjust the value.
M
M
ON
hh
M
hh
--
M
ON
ON
XX °C
E1
E2
E1
E2
HI
M
Code T5200-
TB-9JS0
T5200-
TF-9JS0
Parameter Name
Defaulf Function
01
°F / °C
C
F:
Fahrenheit Degree (°F)
C:
Celsius Degree (°C)
02
Upper limit of set temp
35.0 °C Setting Range 2 ~ 49.5 °C
03
Lower limit of set temp
5.0 °C
Setting Range 0 ~ 47.5 °C
04
Keypad lockout
00
00:
No lock
01:
Lock all keys
02:
Lock ON/OFF key
03:
Lock the keys except ON/OFF key
05
Screen Display
00
00:
Display room temp
01:
Display set temp
06
---
Auto or Manual Mode Switch
00
00:
Manual Mode
01:
Auto Mode
06
---
Key Card Status
01
00: S1, S2
Short Connection indicates key card is
inserted;
Disconnection indicates key card is pulled out
01: S1, S2
Disconnection indicates key card is
inserted;
Short Connection indicates key card is pulled out
07
---
Cooling Temp when key card is pulled out 26.0 °C Setting Range 22 ~ 32 °C
08
---
Heating Temp when key card is pulled out 18.0 °C Setting Range 10 ~ 21 °C