S9210-BxC / S9220-BxC

2

Ordering Codes

Technical Specifications

S 9 2 10 - B D C- 31 A 2-POINT actuator with 2 auxiliary 

switches

-

A

B

C

=

=

=

=

no sensors

with ambient thermosensor

with duct sensor

with duct and ambient sensor

31

32

33

34

=

=

=

=

10 mm Couppler

11 mm Couppler

12 mm Couppler

14 mm Couppler

D

G

=

=

230 VAC

24 V AC/DC

10

20

=

=

10 Nm

20 Nm

Product Codes

S9210-BGC-xxx

S9220-BGC-xxx

S9210-BDC-xxx

S9220-BDC-xxx

ON/OFF

Power Requirements

AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz

Class 2 (North America) or SELV (Europa)

AC 230 V (AC 198 to 264 V) at 50/60 Hz

Power Requirements

- Running

26 VA

0.12 A

0.15 A

- Holding Position

9.3 VA

0.09 A

DC 24 V (DC 21.6 to 26.4 V), Class 2 (North America) or SELV (Europe)

---

- Running

15.6 W

17.6 W

---

-  Holding Position

2.6 W

2.8 W

---

Transformer Sizing Requirements

- Minimum per Actuator

25 VA

---

25 VA

---

Input Signal / Adjustments

---

---

---

---

Auxiliary Switch Rating

Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with Gold Flash Contacts:
AC 24 V, 50 VA Pilot Duty; 
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty; 
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty

Spring Return

Direction is Selectable with Mounting Position of Actuator: 
Side A, Actuator Face Away from Damper for CCW Spring Return; 

Side B, Actuator Face Away from Damper for CW Spring Return

Running and Spring Return Torque

10 Nm

20 Nm for a Single Actuator

10 Nm

20 Nm for a Single Actuator

Rotation Range 

Optional

M9210-603 Adjustable Stop Kit

Optional 

M9220-603 Adjustable Stop Kit

Optional 

M9210-603 Adjustable Stop Kit

Optional 

M9220-603 Adjustable Stop Kit

Adjustable from 30 to 90° CW or CCW Mechanically Limited to 90°

Rotation Time

- Power On (Running

24 to 57 Seconds for 0 to 10 Nm 

at All Operating Conditions 

24 to 57 Seconds for 0 to 20 Nm 

at All Operating Conditions

24 to 57 Seconds for 0 to 10 Nm 

at All Operating Conditions

24 to 57 Seconds for 0 to 20 Nm 

at All Operating Conditions

35 Seconds Nominal at Full Rated Load

- Power Off (Spring Returning)

11 to 15 Seconds for 0 to 10 Nm 

at Room Temperature

35 Seconds maximum 

for 0 to 10 Nm at -30° C

130 Seconds maximum 

for 0 to 10 Nm at -40° C

11 to 15 Seconds for 0 to 20 Nm 

at Room Temperature

35 Seconds maximum 

for 0 to 20 Nm at -30° C

130 Seconds maximum 

for 0 to 20 Nm at -40° C

11 to 15 Seconds for 0 to 10 Nm 

at Room Temperature

35 Seconds maximum 

for 0 to 10 Nm at -30° C

130 Seconds maximum 

for 0 to 10 Nm at -40° C

11 to 15 Seconds for 0 to 20 Nm 

at Room Temperature

35 Seconds maximum 

for 0 to 20 Nm at -30° C

130 Seconds maximum 

for 0 to 20 Nm at -40° C

Cycles

60,000 Full Stroke Cycles; 1,500,000 repositions

Audible Noise Rating

- Power On (Running)

<66 dBA at 1 m

- Power On (Holding)

<18 dBA at 1 m

- Power Off (Spring Returning)

<66 dBA at 1 m

Electrical Connections

(Actuator and Auxiliary Switches)

1.2 m Halogen-Free Cable with 18 AWG (0.75 mm

2

) Wire Leads

Conduit Connections

Integral Connectors for 10 mm Flexible Metal Conduit

Mechanical Connections

- Standard  Shaft Clamp  Available

10, 11, 12, and 14 mm Square Shafts

Aluminum Enclosure

NEMA 2 (IP54) for All Mounting Orientations

Ambient  Conditions

- Operating

-40 to 55° C; 90% RH Maximum, Noncondensing

- Storage

-65 to 85° C; 95% RH Maximum, Noncondensing

Shipping Weight

2.9 kg

3.5 Kg

Dimensions

See Figure 1

  Conformity

EMC Directive 2004/108/EC
Low Voltage Directive 2006/95/EC

Содержание S9210-BC Series

Страница 1: ...Milwaukee Wisconsin USA Branch Offices Principal Cities World wide www johnsoncontrols com S9210 BxC S9220 BxC ON OFF Electric Spring Return Actuators for fire damper P N 14 88360 2374 Rev B Issue Da...

Страница 2: ...S9210 BxC S9220 BxC Figure 7 Angle of rotation limiting Figure 9 S92x0 BDx C ON OFF Control Wiring Diagram Figure 8 S92x0 BGx C ON OFF Control Wiring Diagram Figure 10 Auxiliary Switch Wiring Diagram...

Страница 3: ...sition 2 Rotate the switch adjuster until it points to the desired switch point 3 Connect S2 Auxiliary Switch to a power source or an ohmmeter and apply power to the actuator The actuator moves to the...

Страница 4: ...Stop Kit Adjustable from 30 to 90 CW or CCW Mechanically Limited to 90 Rotation Time Power On Running 24 to 57 Seconds for 0 to 10 Nm at All Operating Conditions 24 to 57 Seconds for 0 to 20 Nm at Al...

Страница 5: ...u commutateur jusqu ce qu il pointe vers le point de commutation d sir 3 Branchez le commutateur auxiliaire S2 une source d alimentation ou un ohmm tre et mettez la commande sous tension Elle passe en...

Страница 6: ...603 En option Kit de fin de course r glable M9210 603 En option Kit de fin de course r glable M9220 603 R glable de 30 90 dans le sens horaire ou anti horaire Limite m canique 90 Temps de rotation So...

Страница 7: ...ten Schaltpunkt zeigt 3 Schlie en Sie den Hilfsschalter S2 an eine Stromquelle oder an ein Ohmmeter an und setzen Sie den Stellantrieb unter Spannung Der Stellantrieb geht zur vollen ffnungsposition u...

Страница 8: ...Adjustable Stop Kit Einstellbarer Begrenzer Bausatz Einstellbar von 30 bis 90 im oder gegen den Uhrzeigersinn begrenzt auf 90 Drehzeit Einschalten Betrieb 24 bis 57 Sekunden f r 0 bis 10 Nm bei allen...

Страница 9: ...re ausiliario S2 1 Spostare l attuatore nella posizione di ritorno a molla completa 2 Ruotare il dispositivo di regolazione dell interruttore fino a portarlo sul limite di commutazione desiderato 3 Co...

Страница 10: ...Regolabile da 30 a 90 in senso orario o antiorario Limitato meccanicamente a 90 Tempo di rotazione Acceso funzionamento Da 24 a 57 secondi per 0 10 Nm in tutte le condizioni di funzionamento Da 24 a...

Страница 11: ...el actuador hasta la posici n de retroceso completo por muelle 2 Gire el ajustador de interruptor hasta que se ale al punto de conmutaci n deseado 3 Conecte el interruptor auxiliar S2 a una fuente de...

Страница 12: ...able M9220 603 opcional Ajustable de 30 a 90 CW o CCW limitado mec nicamente a 90 Tiempo de giro Encendido en funcionamiento 24 a 57 segundos para 0 a 10 Nm en todas las condiciones de funcionamiento...

Страница 13: ...ter en schakel de stroom in naar de bekrachtiger De bekrachtiger gaat en blijft in de volledig geopende positie zolang er stroom op staat 4 Kijk naar het schakelpunt Herhaal indien nodig stap 2 en 3 I...

Страница 14: ...nisch begrensd tot 90 Draaitijd Voeding aan actief 24 tot 57 seconden voor 0 tot 10 Nm bij alle bedrijfsomstandigheden 24 tot 57 seconden voor 0 tot 20 Nm bij alle bedrijfsomstandigheden 24 tot 57 sec...

Страница 15: ...f r brytaren tills den pekar p nskad brytpunkt 3 Anslut den extra brytaren S2 till en str mk lla eller en ohmmeter och str ms tt st lldonet St lldonet flyttas till det helt ppna l get n r str mmen r p...

Страница 16: ...under f r 0 till 10 Nm vid alla driftf rh llanden 24 till 57 sekunder f r 0 till 20 Nm vid alla driftf rh llanden 24 till 57 sekunder f r 0 till 10 Nm vid alla driftf rh llanden 24 till 57 sekunder f...

Страница 17: ...kladu 1 Oto te servopohon do krajn polohy pru inov ho zp tn ho chodu 2 Ot ejte se izovac m prvkem sp na e dokud nebude m it k po adovan mu bodu p epnut 3 P ipojte pomocn sp na S2 ke zdroji nap jen ne...

Страница 18: ...M9210 603 voliteln sada nastaviteln ch zar ek M9220 603 nastaviteln v rozsahu 30 a 90 ve sm ru nebo proti sm ru hodinov ch ru i ek mechanicky omezen na 90 Doba ot en nap jen zapnuto provoz 24 a 57 sek...

Страница 19: ...ej w poni szym przyk adzie 1 Przesun si ownik do po o enia pe nego powrotu spr yny 2 Obraca regulator prze cznika a do osi gni cia danego punktu prze czenia 3 Pod czy prze cznik S2 do r d a zasilania...

Страница 20: ...4 57 sekund dla obci enia 10 Nm we wszystkich warunkach pracy 24 57 sekund dla 0 20 Nm we wszystkich warunkach pracy 24 57 sekund dla obci enia 10 Nm we wszystkich warunkach pracy 24 57 sekund dla 0 2...

Отзывы: