English
IS_M9108-Axx-1N / M9116-Axx-1N / M9124-Axx-1N_14-88360-1955_Rev. B_12 2009
This document is subject to change without notice
2
Rotate the cam wheel
b. clockwise
until the switch button
can be seen. Then tighten-back the Phillips screw in the cam
wheel
b.
.
Factory setting of auxiliary switches
The two auxiliary switches
a.
and
b.
are factory set at the to
approximately 10° CW (
a.
) and 80° CW (
b.
).
Ordering Codes
Codes
Descriptions
M91xx-AGA-1N
Actuator AC/DC 24 V
M91xx-AGC-1N
Actuator AC/DC 24 V with 2 auxiliary switches
M91xx-AGx-1N
Actuator AC/DC 24 V with feedback potentiometer
M91xx-ADA-1N
Actuator AC 230 V
M91xx-ADC-1N
Actuator AC 230 V with 2 auxiliary switches
M91xx-ADx-1N
Actuator AC 230 V with feedback potentiometer
Technical Specifications
Actuators
M9108-
AGx-1N
M9116-
AGx-1N
M9124-
AGx-1N
M9108-
ADx-1N
M9116-
ADx-1N
M9124-
ADx-1N
Drive torque
8 Nm
16 Nm
24 Nm
8 Nm
16 Nm
24 Nm
Damper area
1.5 m
2
3.0 m
2
4.5 m
2
1.5 m
2
3.0 m
2
4.5 m
2
Running time
30 s
80 s
125 s
30 s
80 s
125 s
Indipendent of load, at nominal conditions and room temperature
Power supply
AC 24 V ±20% / DC ±10%
AC 230 V ±15%
Frequency
50-60 Hz
50-60 Hz
Power consumption:
- operating
2.5 W
3.0 W
- at end stops
0.5 W
0.5 W
For wire sizing
5.0 VA / 2 A @ 2ms
3.6 VA / 0.1 A @ 2ms
Weight
1.1 kg
1.2 kg
Control signals
ON/OFF and Floating
Position indication
Mechanical / Potentiometer
Angle of rotation:
- Working range
90° (93° mech.)
- Limiting
5°...85° in 5° steps
Auxiliary switch rating
3 (1.5) A, AC 230 V
Service life
60'000 cycles
Sound power level
45 dB (A)
Protection class
II
Degree of protection
IP 54 (with cable glands, cable downwards)
Temperature: operating/store
-20°...+50°C / -30°...+60°C
Humidity
5...95% RH (not condensing).
Maintenance
Maintenance-free
Conformity
EMC Directive 2004/108/EC:
EN 55011:2007
EN 55022:2006 A1:2007
EN 61000-3-2:2006
EN 61000-3-3:2008
EN 61000-4-2:2001
EN 61000-4-3:2006
EN 61000-4-4:2007
EN 61000-4-5:2006
EN 61000-4-6:2007
EN 61000-4-8 :1994 A1:2001
EN 61000-4-11:2004
EN 61000-6-1:2007
EN 61000-6-3:2007
Low Voltage Directive 2006/95/EC:
EN 60730-1A:2002
EN 60730-2-14:2002