5586996-JSG-A-0120 | Start-Up & Operation Guide
108
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
NetOcc
MV
29520 R/W
NetOcc
Network
Occupancy
Request
A BAS command to request network
occupancy
0 = OCC
1 = UNOCC
2 = not set
ZTSrc
MV
29523
R
ZTSrc
ZT Source
Displays the source of ZT input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
IAQSrc
MV
29528
R
IAQSrc
IAQ Source
Displays the source of IAQ (CO
2
)
input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
SHSrc
MV
29532
R
SHSrc
Space Humidity
Source
Displays the source of
space humidity input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
OprFanReq
MV
29534
R
OprFanReq
Operating Fan
Request
Displays the status of supply fan
request 0 = OFF 1 = ON
FanReqSrc
MV
29535
R
FanReqSrc
Fan Request
Source
Displays the source of supply fan
request input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority"
NetFanReq
MV
29536 R/W
NetFanReq
Network Override
Fan Request
A BAS command that allows user to
request for supply fan
0 = OFF 1 = ON
OATSrc
MV
29542
R
OATSrc
OAT Source
Displays the source of OAT input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
OAQSrc
MV
29548
R
Not Displayed
Locally
Not Displayed
Locally
Displays the source of OAQ (CO
2
)
input
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
Fan-S
MV
29550
R
SupplyF-S
Supply Fan
Status
Displays the active supply fan status
of the unit
0 = OFF/idle
1 = ON/purge
2 = ON/gas valve or limit fault
3 = ON
Table 32: BACnet Points List (Continued)