Johnson Controls
Start-Up & Operation Guide | 5586996-JSG-A-0120
113
Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
ResetLO
MV
29826 R/W
ResetLO
Reset Lockouts
A BAS command to reset lockouts
0 = OFF 1 = ON
HtgAdapTunEn
MV
29881 R/W
HtgAdapTunEn
Heating Adaptive
Tuning Enable
A BAS command to enable heating
adaptive (PID) tuning
0 = NO 1 = YES
ClgAdapTunEn
MV
29882 R/W
ClgAdapTunEn
Cooling Adaptive
Tuning Enable
A BAS command to enable cooling
adaptive (PID) tuning
0 = NO 1 = YES
LoadShedEnable
MV
29883 R/W
LoadShedEnable
Load Shed Active
A BAS command to enable load shed
for automatic demand response
0 = NO 1 = YES
MornC-En
MV
29891 R/W
MornC-En
Morning Cool
Down Enabled
A BAS command to enable morning
cool down 0 = NO 1 = YES
OptStrt-En
MV
29893 R/W
OptStrt-En
Optimal Start
Enabled
A BAS command to enable optimal
start 0 = NO 1 = YES
UnitEn
MV
29896 R/W
UnitEn
Unit Enable
A BAS command to enable/shutdown
the unit 0 = shutdown 1 = enable
HGRUnocc-En
MV
29904 R/W
HGRUnocc-En
HGRH Enabled
for UNOCC
Operation
A BAS command to enable HGRH
for unoccupied operation
0 = NO 1 = YES
SZVAVEn
MV
29908 R/W
SZVAVEn
SZ VAV Enabled
A BAS command to enable SZVAV
0 = OFF 1 = ON
ADR-S
MV
29910
R
ADR-S
Automated
Demand
Response
Displays the automated response
status
0 = NO 1 = YES
OffDurUnocc
MV
29914 R/W
OffDurUnocc
OFF During
UNOCC
A BAS command to disable fan
during UNOCC mode
0 = NO 1 = YES
EconFltDetectEn
MV
29915 R/W
EconFltDetectEn
Economizer Fault
Detection Enabled
A BAS command to enable
economizer FDD
0 = disable 1 = enable
PIDTunRst
MV
29919 R/W
PIDTunRst
PID Tuning Reset
A BAS command to reset PID tuning
0= false 1=true
FrAir-En
MV
29933 R/W
MinOA-En
Min Outside Air
Enabled
A BAS command to enable minimum
outside air damper position
0 = disable 1 = enable
EncodeType
MV
29934 R/W
EncodeType
BACnet Encoding
Type
A BAS command to input BACnet
encoding type
0 = ISO 10646 (UCS-2)
1 = ansi x3.4 (US-ASCII)
2 = Microsoft DBCS code page 932
(Japanese shift JIS)
3 = ISO 10646 (UTF-8)
CF-1A
MV
29935
R
CF-1A
Condenser Fan
1A
Displays the command of condenser
fan CF-1A 0 = OFF 1 = ON
CF-1B
MV
29936
R
CF-1B
Condenser Fan
1B
Displays the command of condenser
fan CF-1B 0 = OFF 1 = ON
CF-2A
MV
29937
R
CF-2A
Condenser Fan
2A
Displays the command of condenser
fan CF-2A 0 = OFF 1 = ON
Table 32: BACnet Points List (Continued)