Operation
Table 26: Menus and Submenus (Continued)
Menu
Submenu
Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Commission
(
FaultOut1
(This menu
applicable only
when building
system
interface board
is connected)
UnitFaults / OFF
OFF, ON
AHUFaults / OFF
OFF, ON
CoolFaults / OFF
OFF, ON
HeatFaults / OFF
OFF, ON
SensorFaults / OFF
OFF, ON
FaultOut2
(This menu
applicable only
when building
system
interface board
is connected)
UnitFaults / OFF
OFF, ON
AHUFaults / OFF
OFF, ON
CoolFaults / OFF
OFF, ON
HeatFaults / OFF
OFF, ON
SensorFaults / OFF
OFF, ON
Manual
Adjustments >
Air Handler
(All of the menu
options default
to 0; allow user
to input offset to
the unit)
ZAH (Zone Humidity Input)
%RH (-10 to 10)
ZT (Zone Temperature Input)
delta deg F (-10 to 10)
BldgPres (Building Static Pressure)
iwg (-1 to 1)
MAT (Mixed Air Temperature)
delta deg F (-10 to 10)
OAT (Outdoor Air Temperature Input)
delta deg F (-10 to 10)
RAT (Return Air Temperature)
delta deg F (-10 to 10)
Return Fan Discharge Pressure
iwg (-1 to 1)
EconDampPos (Economizer Damper
Position)
% open (-10 to 10)
RAD-POS (Return Air Damper Position) % open (-10 to 10)
PFILT-DP (Pre-Filter Differential
Pressure)
iwg (-1 to 1)
FFILT-DP (Final Filter Differential
Pressure)
iwg (-1 to 1)
EA-VP (Exhaust Air Differential
Pressure)
iwg (-1 to 1)
Fr Air (Fresh Air Intake Value)
cfm (-100 to 100)
RAH (Return Air Humidity)
%RH (-10 to 10)
OAH (Outdoor Air Humidity Input)
%RH (-10 to 10)
DA-DP (Discharge Air Differential
Pressure)
iwg (-1 to 1)
DA-P (Discharge Air Static Pressure)
iwg (-1 to 1)
DAT (Discharge Air Temperature)
delta deg F (-10 to 10)
OAQ (Outdoor Air Quality Input)
ppm (-100 to 100)
IAQ (Indoor Air Quality)
ppm (-100 to 100)
DAH (Discharge Air Humidity)
%RH (-10 to 10)
EAHR-T (Exhaust Air Heat Recovery
Temp)
delta deg F (-10 to 10)
HE-T (Heat Entering Temperature)
delta deg F (-10 to 10)