Johnson Controls
5586996-JSG-A-0120 | Start-Up & Operation Guide
104
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
C2B-RunTime
AV
29948
R
C2B-RunTime
Compressor
Accumulated
Runtime 2B
Displays the total runtime for
compressor 2B (hours)
C2B-Starts
AV
29950
R
C2B-Starts
Compressor
Number Times
ON 2B
Displays the compressor 2B start
count
ClgCapLim
AV
29964 R/W
ClgCapLim
Cooling Capacity
Limit
A BAS command to adjust the
cooling capacity limit (0–100%)
CoastTime
AV
29966 R/W
CoastTime
Coast Time
A BAS command for unit to operate
in coast mode (0–120 minutes)
DATCapAlmOffset
AV
29967 R/W
DATCapAlmOffset
DAT Capability
Alarm Offset
A BAS command to adjust alarm
for DAT difference from setpoint
(1.0–10.0°F)
EAHR-T
AV
29970
R
EAHR-T
Exhaust Air Heat
Recovery Temp
Displays the exhaust air energy
recovery temperature (°F)
EF-Flow
AV
29971
R
EF-Flow
Exhaust Flow
Value
Displays the return airflow (CFM)
FFILT-DP
AV
29972
R
FFILT-DP
Final Filter
Differential
Pressure
Displays the final filter differential
pressure (iwg)
H1-Starts
AV
29973
R
H1-Starts
Heating Number
Times ON 1
Displays the heating start counts for
stage 1
H2-Starts
AV
29974
R
H2-Starts
Heating Number
Times ON 2
Displays the heating start counts for
stage 2
H3-Starts
AV
29975
R
H3-Starts
Heating Number
Times ON 3
Displays the heating start counts for
stage 3
H4-Runtime
AV
29977
R
H4-Runtime
Heating Stage
4 Accumulated
Runtime
Displays the total runtime for stage 4
heating (hours)
H4-Starts
AV
29979
R
H4-Starts
Heating Number
Times ON 4
Displays the heating start counts for
stage 4
H5-Runtime
AV
29981
R
H5-Runtime
Heating Stage
5 Accumulated
Runtime
Displays the total runtime for stage 5
heating (hours)
H5-Starts
AV
29983
R
H5-Starts
Heating Number
Times ON 5
Displays the heating start counts for
stage 5
H6-Runtime
AV
29985
R
H6-Runtime
Heating Stage
6 Accumulated
Runtime
Displays the total runtime for stage 6
heating (hours)
H6-Starts
AV
29987
R
H6-Starts
Heating Number
Times ON 6
Displays the heating start counts for
stage 6
H7-Runtime
AV
29989
R
H7-Runtime
Heating Stage
7 Accumulated
Runtime
Displays the total runtime for stage 7
heating (hours)
H7-Starts
AV
29991
R
H7-Starts
Heating Number
Times ON 7
Displays the heating start counts for
stage 7
H8-Runtime
AV
29993
R
H8-Runtime
Heating Stage
8 Accumulated
Runtime
Displays the total runtime for stage 8
heating (hours)
Table 32: BACnet Points List (Continued)