Technical specifications
Table 10: FX-PCV1615/1626/1628/1630 Controllers
Product Code Numbers
FX-PCV1615-x:
Integrated VAV Box Controller, Actuator and
Pressure Sensor: 3 UI, 2 BO, 24 VAC; FC and SA Bus
FX-PCV1626-x:
Integrated VAV Box Controller/Actuator (No
Pressure Sensor - DPT); 3 UI, 3 BO, and 2 CO; 24 VAC; FC and SA
Bus
FX-PCV1628-x:
Integrated VAV Box Controller/ (No Actuator)
Pressure Sensor - DPT; 3 UI, 3 BO, and 2 CO; 24 VAC; FC and SA
Bus
FX-PCV1630-x:
32-bit, Integrated VAV Controller/Actuator/
Pressure Sensor - DPT; 3 UI, 3 BO, and 2 CO; 24VAC; FC and SA
Bus
Communications Protocol
BACnet MSTP, N2
Supported Supervisors
FX80, FX Server
Supply Voltage
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz,
Power Supply Class 2 (North America), Safety Extra-Low Voltage
(SELV) (Europe)
Power Consumption
10 VA typical, 14 VA maximum
Note:
The VA rating does not include any power supplied to
the peripheral devices connected to Binary Outputs (BOs)
or Configurable Outputs (COs), which can consume up to
12 VA for each BO or CO, for a possible total consumption
of an additional 60 VA (maximum).
Ambient Conditions
Operating:
0°C to 50°C (32°F to 122°F)
Storage:
-40°C to 70°C (-40°F to 158°F)
Terminations
Inputs/Outputs: 6.3 mm (1/4 in.) Spade Lugs
FC Bus, SA Bus, and Supply Power: 4-Wire and 2-Wire Pluggable
Screw Terminal Blocks
SA Bus Modular Ports: RJ-12 6-Pin Modular Jacks
27
FX-PCV1615/1626/1628/1630 Programmable VAV Box Controllers Installation Instructions