RWF ROTARY SCREW COMPRESSOR UNITS
MAINTENANCE
S70-600 IOM (OCT04)
Page 34
TROUBLESHOOTING THE RWF COMPRESSOR
SYMPTOM
PROBABLE CAUSES and CORRECTIONS
EXCESSIVE NOISE and VIBRATION
Main oil injection valve may be closed. Open valve.
Bearing damage or excessive wear. CONTACT Frick Factor or Frick service.
Coupling loose on shaft. Tighten coupling. Replace if damaged.
If motor or compressor have been reinstalled,
check that installation done according to S70-660 SM
Refrigerant flood back. Correct system problem.
SLIDE VALVE and/or SLIDE STOP
4-way hydraulic control valve failed. Repair or replace.
WILL NOT MOVE
Slide stop indicator rod stuck. Contact Frick Factor or Frick service for assistance.
Check both S.V. and S.S. feedback devices for wiring and resistance.
Compressor must be running with sufficient oil pressure.
Unloader piston stuck. Contact Frick Factor or Frick service for assistance.
Slipper seals worn out or damaged. Contact Frick Factor or Frick service for assistance.
NOTE: Troubleshooting the compressor is limited to identifying the probable cause. If a mechanical problem is suspected contact the
Service Department, Frick . DO NOT ATTEMPT TO DISASSEMBLE COMPRESSOR.
TROUBLESHOOTING THE OIL SEPARATION SYSTEM
SYMPTOM
PROBABLE CAUSES and CORRECTIONS
GRADUAL OIL LOSS WITH AN OIL
Maintaining too high an oil level, lower level.
LEVEL IN THE COALESCER
SECTION SIGHT GLASS
Refrigerant carryover or liquid injection overfeed ing, correct operation.
Loss of suction superheat. Adjust evaporator feeds.
Contaminated oil, damaged or not seated coalescer filter elements. Replace
oil charge and coalescers.
Coalescer return valve closed. Open return valve.
Coalescer return valve closed. Open valve.
Coalescing oil return line strainer blocked. Clean.
Needle valve blocked. Clean.
RAPID OIL LOSS WITH NO OIL
On shutdown, compressor unit suction check valve did not close. Repair valve.
LEVEL IN THE COALESCER
SECTION SIGHT GLASS
Suction check valve bypass valve open. Close valve.
Coalescers loose or not seated properly. Correct or replace.
On economized unit: economizer check valve not working. Repair or replace.
Economizer check valve not in automatic position or manually opened. Place in auto position.
SHAFT SEAL LEAKAGE
If leakage exceeds normal allowable rate of 7 drops per minute, replace seal.
Содержание Frick RWF 100
Страница 40: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM OCT04 Page 40 P I DIAGRAM ...
Страница 43: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM OCT04 Page 43 P I DIAGRAM LIQUID INJECTION BOOSTER ...
Страница 52: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM OCT04 Page 52 OPERATING LOG SHEET ...
Страница 57: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM OCT04 Page 57 ...