background image

ECH EVAPORATIVE CONDENSERS

MAINTENANCE

140.910-IOM (DEC 13)

Page 19

  In order to optimize heat transfer efficiency and maximize 

equipment  life  “bleed”  or  “blowdown”  a  small  amount 
of  recirculating  water  from  the  system.  This  controls  the 
cycles  of  concentration  to  maintain  the  quality  of  the 
recirculating  water  within  the  guidelines  given  in  Table 
2,  under  Corrosion  and  Scale  Control  in  the  OPERATION 
section.

  Replenish  the  “bleed”  water  with  fresh  makeup  water, 

thereby limiting the buildup of impurities.

  Bleed/Blowdown:

 

1.  Accomplish  the  bleed  automatically  through  a 

solenoid valve controlled by a conductivity meter. The 
conductivity meter set point is the water conductivity 
at  the  desired  cycles  of  concentration  and  should  be 
determined by a competent water treatment expert.

NOTICE

The  solenoid  valve  and  conductivity  meter  must  be 
supplied by others.

 

2.  Alternatively, use a bleed line with a valve to continuously 

bleed from the system. In this arrangement, adjust the 
rate of bleed using the valve in the bleed line. Measure 
the rate of bleed by filling a container of known volume 
while  noting  the  duration.  Check  the  bleed  rate  and 
water  quality  periodically  to  ensure  that  adequate 
control of the water quality is being maintained.

Bleed Line Calculations:

 Bleed rate is determined by the fol-

lowing formula:

Bleed Rate = B =

E

(n-1)

 

Where:

  B = Bleed Rate (GPM)

 

E* = Evaporation Rate (GPM) = Q (GPM) x R (°F) x .001

 

Q = Process Fluid Flow Rate (GPM)

 

R = Range

 

n = Number of Cycles of Concentration = CR/CM

 

CR = Concentration in Recirculating Water

 

CM = Concentration in Makeup Water

* The evaporation rate “E” can be determined by any one of 
the following methods:

1. The evaporation rate is approximately 2 GPM per 1 million 
BTUH of heat rejection.

2. The evaporation rate is approximately 3 GPM per 100 tons 
of refrigeration.

3.  Evaporation  Rate  =  Q  (GPM)  x  R  x  .001  (as  shown  in  the 
example).

The following example illustrates a bleed rate calculation:

Given:

  Condenser

  Process Fluid Flow Rate = 800 GPM

  Maximum Allowable Chloride Concentration = 250 ppm

  Concentration of Chlorides in Makeup Water = 45 ppm

  Range = 10°F

Find:

 Bleed Rate

Solution:

 So in this case,

E = Q x R x 0.001 = 800 x 10 x 0.001 = 8 GPM

n =

CR

=

250 ppm

= 5.55

CM

45 ppm

Bleed Rate = B =

E

=

8 GPM

= 1.75 GPM

(n-1)

(5.55-1)

Therefore, in this case we must bleed approximately 1.75 GPM 
to limit the concentration of impurities.

NOTICE

This  example  focuses  on  a  single  parameter  (chloride 
concentration) of water only. The bleed rate required for a 
system (when evaluating more than one parameter) is the 
highest bleed rate required to keep all parameters within 
recommended limits.

Содержание Frick ECH

Страница 1: ...ECH D Evaporative Condensers Please check www jci com frick for the latest version of this publication THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFO...

Страница 2: ...if Extended Downtime is a Concern 21 INSTALLATION Rigging and Assembly Instructions ECH ech d Evaporative Condensers 4 Shipping 4 Check Unit Before Rigging 4 Anchoring 4 Rigging 5 Section Assembly of...

Страница 3: ...ift Eliminators Spray Water Distribution System Power Train Axial Fan s Single Side Air Inlet ECH Dual Air Inlet ECH D Suction Strainer Spray Riser Pipe Bleed Valve Spray Pump Access Door Spray Pump M...

Страница 4: ...pe required to assemble sections or component parts are furnished by Frick and are shipped with the unit A checklist inside the envelope attached to the side of the unit marked Contractor s Installati...

Страница 5: ...tance between the spreader bar attachment points Figure 1 Two Section Units Figure 2 Plenum and Coil Sections Figure 3 Lower Section Two Section Units Four Section Units Model Number Section H W1 W2 E...

Страница 6: ...ler tape on the edge flange as shown in Figure 5 For multiple cell installations remove tie down plates from plenum and coil sections prior to setting sections Using drift pins in the bolt holes provi...

Страница 7: ...ith bolt hole at one corner and following down the flange Screw in place using the self tapping screws or bolts supplied with the unit to ensure leak free operation Figure 7 Assembly of Two Section Un...

Страница 8: ...for more details WARNING Do not perform any service on or near the fans motors drives or inside the unit without first ensuring that the fans and the pumps are disconnected and locked out NOTICE 1 Re...

Страница 9: ...in strainer and re install Cover the fan discharge opening to keep out dirt and debris Lubricate the fan shaft bearings motor base and motor base adjusting screw Close the shutoff valve in the makeup...

Страница 10: ...ambient temperature is below freezing Contact your local Frick Representative for guidelines on the installation of an emergency coil drain system Further protection against coil freeze up is possibl...

Страница 11: ...mall portion of the recirculating water to a drain is used to control the concentration of dissolved solids On rare occasions this may be adequate to control scale and corrosion More often however che...

Страница 12: ...Start up and Start up Following a Shutdown Period 1 To minimize the risk of biological contamination during a shutdown period of three days or more it is recommended that the entire system evaporativ...

Страница 13: ...ingle speed fan motors and drive assemblies One drive assembly is sized for full speed and load and the other is sized for approximately 2 3 speed and consumes only 1 3 the design horsepower The Senti...

Страница 14: ...belt deflects be tween 1 4 and 3 8 as shown in Figures 12a and 12b Belt tension adjustment if required 1 Loosen the lock nut on the motor base adjusting screw 2 Turn the motor base adjusting screw cl...

Страница 15: ...th the unit idle Add oil if level is below the oil level sight glass The standard oil provided is mineral oil Synthetic lubricants are also available as an option see Table 5 Refer to Table 6 for norm...

Страница 16: ...ties Service Oil Citgo Pacemaker 220 Conoco Hydroclear Multipurpose R O Oil 220 Exxon Teresstic 220 GulfOil Harmony 220 MobilOil DTE Oil BB Pennzoil Pennzbell TO 220 Philips Petroleum Magnus 220 Shell...

Страница 17: ...nal Start up Purge both bearings with new grease prior to start up 3 Operation Purge bearings every 2 000 hours of operation or once every 3 months whichever occurs first 4 Extended Shutdown Purge bea...

Страница 18: ...ent accumulations of scale corrosion sludge or biological growth which could interfere with the electrical circuit The water level is maintained at the recommended operating level regardless of the sy...

Страница 19: ...ontrol of the water quality is being maintained Bleed Line Calculations Bleed rate is determined by the fol lowing formula Bleed Rate B E n 1 Where B Bleed Rate GPM E Evaporation Rate GPM Q GPM x R F...

Страница 20: ...se adjusting screw X X X Check and lubricate optional gear drive See gear drive section for detailed instructions and schedule Check drive alignment X Check motor voltage and current X X X Clean fan m...

Страница 21: ...inventory of commonly used parts Even with this fast delivery capability it is still recommended that certain essential emergency repair parts be maintained in your local inventory to minimize any po...

Страница 22: ...ech Evaporative Condensers notes 140 910 IOM DEC 13 Page 22...

Страница 23: ...ech Evaporative Condensers notes 140 910 IOM DEC 13 Page 23...

Страница 24: ...Page 24 Johnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www jci com frick Form 140 910 IOM 2013 12 Supersedes 140 910 IOM 2009 11 Subject to change with...

Отзывы: