background image

ECH EVAPORATIVE CONDENSERS

MAINTENANCE

140.910-IOM (DEC 13)

Page 17

Adjustable Motor Base

Coat  the  motor  base  slides  and  adjusting  screws  (see  Figure 
10 in the Operation section) every 3 months using good quality 
corrosion inhibiting grease such as one of those recommended 
for lubricating the fan shaft bearings below.

 

WARNING

Check to ensure the controls for the fan motor are set to 
allow a maximum of 6 on-off cycles per hour.

FAN SHAFT BEARINGS

Two pillow block ball bearings support the fan shaft. Each bearing 
is equipped with a lubrication fitting and a slinger/locking collar 
to keep out moisture.

Inspection and Maintenance

  Lubricate the bearings with only a manual grease gun. Do 

not use high-pressure grease guns since they may rupture 
the bearing seals.

  Lubricate  the  bearings  with  only  one  of  the  following 

compatible  water  resistant  greases*  which  are  suitable 
for ambient temperatures ranging from -65°F (-53.9°C) to 
+250°F (121.1°C).

Amoco-Rycon Premium#3 

 MobilGrease

®

-AW2 

Chevron-SRI 

 Shell-Alvania RL3™ 

Citgo-Polyurea MP2™ 

 Shell-Alvania #3 

Conoco-Polyurea 2™ 

 Shell-Dolium “R” 

Exxon-Polyrex

®

 EM 

 SKF-LGHP2™ 

Exxon-Unirex N™ 

 Unocal76-Unilife Grease™ 

*NOTE: List of brand names is for identification only and are 
not exclusive recommendations.

  Lubricate the bearings as follows: 

 

1. 

Initial  Start-up:

  Normally,  no  lubrication  is  required 

since the bearings have been lubricated at the factory 
prior to shipment. However, if the unit has been stored 
at  the  job  site  for  more  than  1  year,  both  bearings 
should  be  lubricated  with  new  grease  before  initial 
operation. 

When  lubricating,  purge  the  old  grease 

from  the  bearing  by  gradually  adding  grease  until 
a  bead  of  new  grease  appears  at  the  seal  on  the 
underside of the bearing.

 

 

2. 

Seasonal  Start-up:

  Purge  both  bearings  with  new 

grease prior to start-up.

 

3. 

Operation:

  Purge  bearings  every  2,000  hours  of 

operation  or  once  every  3  months,  whichever  occurs 
first.

 

4. 

Extended Shutdown:

 Purge bearings with new grease 

prior to any prolonged storage or downtime.

HEAT TRANSFER SECTION

Fill and Drift Eliminator

The ECH has PVC fill with integral drift eliminators.

Inspection and Maintenance:

  Inspect  and  clean  the  fill  with  the  integral  eliminators  at 

least quarterly.

  The inspection procedure is as follows:

 

1.  Shut off the fan and the spray pump.

 

2.  Inspect the fill for obstructions, damage and fouling.

  Remove any obstructions from the fill.

  Remove  any  minor  fouling  chemically.  Contact  your  local 

water treatment consultant for advice.

  Major  fouling  requires  cleaning  and  flushing.  Follow  the 

procedures listed in the SYSTEM CLEANING section at the 
end of the MAINTENANCE section.

WATER DISTRIBUTION SYSTEM

The water is distributed through a corrosion resistant polyvinyl 
chloride  (PVC)  system.  The  fill  and  drift  eliminators  are  also 
made of PVC, which requires no protection against rot, decay, 
rust, or biological attack.

Inspect and clean the spray nozzles and heat transfer section 
each month. 

The inspection procedure is as follows:

  Shut off the fan, but leave the spray pump running.

  Check to see if the nozzles are producing the spray pattern 

shown in Figure 15.

Figure 15 - Nozzle Spray Pattern

  Clean  any  nozzles  which  are  clogged.  If  necessary,  the 

nozzle and rubber grommet may be removed for cleaning.

  Inspect  the  coil  surface.  Any  corrosion,  damage,  or 

obstructions must be corrected. 

 

CAUTION

Don’t  use  steam  or  high  pressure  water  to  clean  PVC 
eliminators or materials other than steel.

WATER LEVEL CONTROL

There are two types of water level controls used on Frick units:

  Mechanical makeup valve assembly

  Optional electric water level control package

The  ECH  water  makeup  valve  assembly  is  located  on  the  air 
inlet face.

Содержание Frick ECH

Страница 1: ...ECH D Evaporative Condensers Please check www jci com frick for the latest version of this publication THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFO...

Страница 2: ...if Extended Downtime is a Concern 21 INSTALLATION Rigging and Assembly Instructions ECH ech d Evaporative Condensers 4 Shipping 4 Check Unit Before Rigging 4 Anchoring 4 Rigging 5 Section Assembly of...

Страница 3: ...ift Eliminators Spray Water Distribution System Power Train Axial Fan s Single Side Air Inlet ECH Dual Air Inlet ECH D Suction Strainer Spray Riser Pipe Bleed Valve Spray Pump Access Door Spray Pump M...

Страница 4: ...pe required to assemble sections or component parts are furnished by Frick and are shipped with the unit A checklist inside the envelope attached to the side of the unit marked Contractor s Installati...

Страница 5: ...tance between the spreader bar attachment points Figure 1 Two Section Units Figure 2 Plenum and Coil Sections Figure 3 Lower Section Two Section Units Four Section Units Model Number Section H W1 W2 E...

Страница 6: ...ler tape on the edge flange as shown in Figure 5 For multiple cell installations remove tie down plates from plenum and coil sections prior to setting sections Using drift pins in the bolt holes provi...

Страница 7: ...ith bolt hole at one corner and following down the flange Screw in place using the self tapping screws or bolts supplied with the unit to ensure leak free operation Figure 7 Assembly of Two Section Un...

Страница 8: ...for more details WARNING Do not perform any service on or near the fans motors drives or inside the unit without first ensuring that the fans and the pumps are disconnected and locked out NOTICE 1 Re...

Страница 9: ...in strainer and re install Cover the fan discharge opening to keep out dirt and debris Lubricate the fan shaft bearings motor base and motor base adjusting screw Close the shutoff valve in the makeup...

Страница 10: ...ambient temperature is below freezing Contact your local Frick Representative for guidelines on the installation of an emergency coil drain system Further protection against coil freeze up is possibl...

Страница 11: ...mall portion of the recirculating water to a drain is used to control the concentration of dissolved solids On rare occasions this may be adequate to control scale and corrosion More often however che...

Страница 12: ...Start up and Start up Following a Shutdown Period 1 To minimize the risk of biological contamination during a shutdown period of three days or more it is recommended that the entire system evaporativ...

Страница 13: ...ingle speed fan motors and drive assemblies One drive assembly is sized for full speed and load and the other is sized for approximately 2 3 speed and consumes only 1 3 the design horsepower The Senti...

Страница 14: ...belt deflects be tween 1 4 and 3 8 as shown in Figures 12a and 12b Belt tension adjustment if required 1 Loosen the lock nut on the motor base adjusting screw 2 Turn the motor base adjusting screw cl...

Страница 15: ...th the unit idle Add oil if level is below the oil level sight glass The standard oil provided is mineral oil Synthetic lubricants are also available as an option see Table 5 Refer to Table 6 for norm...

Страница 16: ...ties Service Oil Citgo Pacemaker 220 Conoco Hydroclear Multipurpose R O Oil 220 Exxon Teresstic 220 GulfOil Harmony 220 MobilOil DTE Oil BB Pennzoil Pennzbell TO 220 Philips Petroleum Magnus 220 Shell...

Страница 17: ...nal Start up Purge both bearings with new grease prior to start up 3 Operation Purge bearings every 2 000 hours of operation or once every 3 months whichever occurs first 4 Extended Shutdown Purge bea...

Страница 18: ...ent accumulations of scale corrosion sludge or biological growth which could interfere with the electrical circuit The water level is maintained at the recommended operating level regardless of the sy...

Страница 19: ...ontrol of the water quality is being maintained Bleed Line Calculations Bleed rate is determined by the fol lowing formula Bleed Rate B E n 1 Where B Bleed Rate GPM E Evaporation Rate GPM Q GPM x R F...

Страница 20: ...se adjusting screw X X X Check and lubricate optional gear drive See gear drive section for detailed instructions and schedule Check drive alignment X Check motor voltage and current X X X Clean fan m...

Страница 21: ...inventory of commonly used parts Even with this fast delivery capability it is still recommended that certain essential emergency repair parts be maintained in your local inventory to minimize any po...

Страница 22: ...ech Evaporative Condensers notes 140 910 IOM DEC 13 Page 22...

Страница 23: ...ech Evaporative Condensers notes 140 910 IOM DEC 13 Page 23...

Страница 24: ...Page 24 Johnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www jci com frick Form 140 910 IOM 2013 12 Supersedes 140 910 IOM 2009 11 Subject to change with...

Отзывы: