8.10 Power Saving/Operation Noise
Reduction Schedule
This function is used to start or stop the power
saving or the noise reduction at the desired time.
It is possible to set the power saving or the
operation noise reduction schedule up to
fi
ve times
a day each day.
The “Power Saving Schedule” setting performs the
scheduled control of the mode set by the “Power
Saving” mode.
NOTE:
• Set time zones so they don’t overlap during a
day when managing multiple schedule patterns
as in Example 1 below. If time zones are
overlapped as in Example 2, the
fi
rst “Time
OFF” is cancelled.
Example of Power Saving Operation and
Schedule Setting
Example of Power Saving Schedule Operation
Example 1
Example 2
(1) Select “Sav/Reduction Schedule” from the
“Menu” screen and press “OK”.
The power saving/operation noise reduction
schedule setting screen is displayed as “Sav/
Reduction Schedule”.
When using a Sub controller or if the
indoor unit does not support power saving,
the power saving schedule setting of the
“Intermittent Control” is displayed.
Refer to (3) below.
(2) By pressing “ ” or “ ”, select the setting
item.
The setting changes as follows:
“Capacity Control”
↔
“Intermittent Control”
↔
“Noise Reduction”
Press “OK”.
The power saving schedule setting (or noise
reduction schedule) screen is displayed as
“Sav/Reduction Schedule”.
(3) Select the “Day/Time Setting” with “ ” or “
” and press “OK”.
The weekly schedule setting screen is
displayed.
When the current time is not set, the “Time
Adjusting” screen is displayed automatically.
CORRECT
INCORRECT
MED
LOW
HIGH
OFF
ON
08:00
㻌
10:00
12:00 14:00 16:00 18:00
1
2
3
4
5
Menu
Function 10
Sav/Reduction Schedule
Comfort Setting
Quick Function
02
/
05
Operation Noise Reduction
15:10(Fri)
Entr
Rtrn
Sel.
Back
OK
Sav/Reduction Schedule
Noise Reduction
Intermnt Control
Capacity Control
15:10(Fri)
Entr
Rtrn
Sel.
Back
Set when schedule is used.
※
Power
Saving mode setting activated too.
OK
Capacity Control
Schedule ON/OFF
Day/Time Setting
15:10(Fri)
Entr
Rtrn
Sel.
Back
Set when schedule is used.
※
Power
Saving mode setting activated too.
OK
Back
OK
Capacity Control (Mon)
1
2
3
4
5
15:10(Fri)
Entr
Rtrn
Sel.
Adj.
LOW
MED
MED
HIGH
08:00
10:00
10:00
12:00
14:00
16:00
12:00
14:00
16:00
18:00
LOW
Back
OK
Capacity Control (Mon)
1
2
3
4
5
15:10(Fri)
Entr
Rtrn
Sel.
Adj.
LOW
MED
HIGH
08:00
18:00
10:00
12:00
16:00
14:00
OK
Menu
Back/Help
OK
Menu
Back/Help
OK
Menu
Back/Help
OK
Menu
Back/Help
OK
Menu
Back/Help
OK
Menu
Back/Help
Содержание CIW01
Страница 2: ......
Страница 50: ......
Страница 51: ......
Страница 52: ...Code No LIT 12013123 Issued September 2019 P5415479 rev 4 2017 Johnson Controls Inc ...