www.johnsonandstarley.co.uk
16
10
FIGURE 14. CONTROL PANEL
FIGURE 15. LED READ OUT
CONTROL PANEL
1
Time control
2
A +
3
B -
4
LED Display
5
E +
6
D -
7
Summer Air Circulation
8
C
9
Reset
LED READ OUT
1
Open therm symbol
2
Installer mode
indicator
3
Service indicator
4
Stand by
5
Degrees
6
Error - ‘e’ or celsius - ‘c’
7
Reset button indicator
8
Flame indicator
9
Button ‘c’ indication
10
Summer circulation
11
Central heating
11
1
2
3
4
7
6
8
9
5
1
2
3
4
5
6
7
9
8
13.
FITTING INSTRUCTIONS
CAUTION: This appliance exceeds the recommended weight for a one man lift as detailed in the Manual
Handling Operations, 1992 Regulations.
It should be noted that this appliance could contain sharp edges and care MUST be taken when handling.
13.1
FITTING THE APPLIANCE
13.1.1 Making sure the plenum is clear from all debris, lift the appliance into place.
13.1.2 Using a spirit level it is important the appliance is completely level, this appliance MUST NOT lean or tilt
in any direction. This will cause problems with the condense draining.
13.1.3 Seal the unit to the plenum, using ducting tape (not supplied). Ensure a good seal is made.
13.1.3 Installation of the condense tube is a maximum of 10 meters. There should be no trapped kinks in this
length of tube.
13.1.4 Fix all connections to the appliance ready for commissioning.
14. COMMISSIONING
14.1
After installation of the appliance, you MUST do the following:
14.1.1 Test for gas leakage using proprietary detection fluid and seal any leaks found.
14.1.2 Carry out preliminary electrical system checks.
14.1.3 Ensure that:
a. the filter, fan and fan compartments are free from obstructions.
b. all registers or grilles are open and conform to design specifications.
c. the return, relief and ventilation air installations are adequate.
14.2
Switch the air heater electrical Supply ON.
14.3.
To fill the flue condensate trap, disconnect the sliding flue connector and slowly pour tap water into the elbow
until you hear the condensate pump operating. Failure to do this will result in a whistling sound. Check for leaks.
NOTE:
The appliance must be connected to the mains for the pump to operate.
14.4
SYSTEM BALANCING
14.4.1 Press button ‘7’ to put the appliance into Summer Air Circulation mode.
14.4.2 Balance the system to provide the required volume proportions at the warm air outlets.