www.johnsonandstarley.co.uk
38
Should a fault occur, the boiler will shut down and these blocking codes will be displayed.
FLOW THERMISTOR FAULT
YES
YES
Is the wiring securely connected to the low voltage 9 way connector X5 on
the PCB?
NO
NO
Securely connect the wiring to the flow Thermistor.
Fit new Thermistor.
Is the wiring securely connected to the Flow thermistor?
Disconnect the wiring from the Flow Thermistor.
Check the resistance using a suitable multi-meter connected across the
Thermistor’s terminal pins.
Is the Thermistor value correct?
Check & replace as necessary.
YES
NO
Replace the PCB.
Should a fault occur, the boiler will shut down and these blocking codes will be displayed.
EXHAUST SENSOR FAULT
BLOCKING CODES
YES
YES
YES
Check wiring & connections to 9 way connector on PCB X5.
Replace PCB.
NO
NO
NO
Fill and vent the system and open all isolation
valves, check as supply, then reset boiler
Replace the flue thermistor.
Secure to PCB.
Is the boiler & CH system filled with water and all isolation & radiator
valves open?
Check flue thermistor. Check resistance using a suitable multi-meter
connection across the thermistor’s terminal pins. (Refer to graph on E03).
REMOTE RESET LOCKOUT
Turn power on and off, reset boiler. Boiler will correct original lockout error.
LOW POWER SUPPLY FROM MAINS
YES
NO
Correct electrical fault.
Is mains supply to boiler between 190V - 256V @ 50 Hz?
Replace PCB.
LOW WATER PRESSURE
YES
YES
Replace Water Pressure Sensor.
NO
NO
Fill and vent the system and open all isolation
valves, check as supply, then reset boiler
Re-fit connections.
Is the boiler & CH system filled with water and all isolation valves open.
(check pressure gauge is between 1 & 1.5bar)?
Are connections on water pressure sensor secure?