CLIZIA D LOW NOX 24 A
12
EN
cod. 3541D140 - Rev. 00 - 10/2012
2.4 Adjustments
Summer/Winter Switchover
Press the
summer/winter
button (detail 6 - fig. 17) for 2 seconds.
The display activates the Summer symbol (detail 10 - fig. 17): the boiler will only deliver
domestic hot water. The antifreeze system remains activated.
To deactivate the Summer mode, press the
summer/winter
button (detail 6 - fig. 17)
again for 2 seconds.
Heating temperature adjustment
Use the heating buttons (details 3 and 4 - fig. 17) to vary the temperature from a min. of
30°C to a max. of 80°C; in any case, it is advisable not to operate the boiler below 45°C.
fig. 4
Domestic hot water (DHW) temperature adjustment
Use the DHW buttons (details 1 and 2 - fig. 17) to adjust the temperature from a min. of
40°C to a max. of 55°C.
fig. 5
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms. If the room ther-
mostat is not installed, the boiler will keep the system at the set system delivery setpoint
temperature.
Room temperature adjustment (with optional remote timer control)
Using the remote timer control, set the required temperature in the rooms. The boiler will
adjust the system water according to the required room temperature. For operation with
remote timer control, please refer to the relevant instruction manual.
ECO/COMFORT selection
The unit has a function that ensures a high domestic hot water delivery speed and max-
imum comfort for the user. When the device is activated (COMFORT mode), the water
contained in the boiler is kept hot, thereby ensuring immediate availability of hot water
on opening the tap, without waiting times.
The user can deactivate the device (ECO mode) by pressing the
eco/comfort
button
(detail 7 - fig. 17). In ECO mode the display activates the ECO symbol (detail 12 - fig. 17).
To activate the COMFORT mode, press the
eco/comfort
button (detail 7 - fig. 17) again.
Sliding Temperature
When the optional external probe is installed, the boiler adjustment system works with
"Sliding Temperature”. In this mode, the temperature of the heating system is controlled
according to the outside weather conditions, to ensure high comfort and energy saving
throughout the year. In particular, the system delivery temperature is decreased as the
outside temperature increases, according to a specific "compensation curve”.
With Sliding Temperature adjustment, the temperature set with the heating buttons (de-
tail 3 - fig. 17) becomes the maximum system delivery temperature. It is advisable to set
a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. Possible
adjustments can in any case be made by the user to improve comfort.
Compensation curve and curve offset
Press the
reset
button (detail 6 - fig. 17) for 5 seconds to access the "Sliding tempera-
ture" menu; the display shows "CU" flashing.
Use the DHW buttons (detail 1 - fig. 17) to adjust the curve from 1 to 10 according to the
characteristic. By setting the curve to 0, sliding temperature adjustment is disabled.
Press the heating buttons (detail 3 - fig. 17) to access parallel curve offset; the display
shows "OF" flashing. Use the DHW buttons (detail 1 - fig. 17) to adjust the parallel curve
offset according to the characteristic (fig. 22).
Press the
reset
button (detail 6 - fig. 17) again for 5 seconds to exit the "Sliding Temper-
ature" menu.
If the room temperature is lower than the required value, it is advisable to set a higher
order curve and vice versa. Proceed by increasing or decreasing in steps of one and
check the result in the room.
fig. 6 - Example of compensation parallel curve offset
Adjustments from Remote Timer Control
A
If the Remote Timer Control (optional) is connected to the boiler, the above ad-
justments are managed according to that given in table 4.
Table. 1
System water pressure adjustment
The filling pressure with system cold, read on boiler water gauge (detail 17 - fig. 17), must
be approx. 1.0 bar. If the system pressure falls to values below minimum, the boiler stops
and fault
F37
is displayed. Operate the filling cock detail 1 fig. 23 and bring it to the initial
value. Always close the filling cock at the end of the operation.
fig. 7 - Filling cock
I I I I
II
II
I
I I I I
II
II
I
Heating temperature setting
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
DHW temperature adjustment
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Summer/Winter Switchover
Summer mode has priority over a possible Remote Timer Control
heating demand.
Eco/Comfort selection
On disabling DHW from the Remote Timer Control menu, the
boiler selects the Economy mode. In this condition, the
eco/com-
fort
button (detail 7 - fig. 17) on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the
boiler selects the Comfort mode. In this condition it is possible
select one of the two modes with the
eco/comfort
button (detail 7
- fig. 17) on the boiler panel.
Sliding Temperature
Both the Remote Timer Control and the boiler card manage Slid-
ing Temperature adjustment: the boiler card Sliding Temperature
has priority.
20
30
40
50
60
70
80
90
85
20
10
0
-10
-20
1
2
3
4
5
6
8
9
10
7
20
10
0
-10
-20
20
30
40
50
60
70
80
90
85
1
2
3
4
5
6
8
9
10
7
OFFSET = 20
OFFSET = 40
1
Содержание CLIZIA D LOW NOX 24 A
Страница 39: ......