CLIZIA D 24 A
11
EN
cod. 3541C830 - Rev. 00 - 09/2012
Domestic hot water (DHW) temperature adjustment
Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a min. of
40°C to a max. of 55°C.
fig. 5
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms. If the room ther-
mostat is not installed, the boiler will keep the system at the set system delivery setpoint
temperature.
Room temperature adjustment (with optional remote timer control)
Using the remote timer control, set the required temperature in the rooms. The boiler will
adjust the system water according to the required room temperature. For operation with
remote timer control, please refer to the relevant instruction manual.
ECO/COMFORT selection
The unit has a function that ensures a high domestic hot water delivery speed and max-
imum comfort for the user. When the device is activated (COMFORT mode), the water
contained in the boiler is kept hot, thereby ensuring immediate availability of hot water
on opening the tap, without waiting times.
The user can deactivate the device (ECO mode) by pressing the
eco/comfort
button
(detail 7 - fig. 1). In ECO mode the display activates the ECO symbol (detail 12 - fig. 1).
To activate the COMFORT mode, press the
eco/comfort
button (detail 7 - fig. 1) again.
Sliding Temperature
When the optional external probe is installed, the boiler adjustment system works with
"Sliding Temperature”. In this mode, the temperature of the heating system is controlled
according to the outside weather conditions, to ensure high comfort and energy saving
throughout the year. In particular, the system delivery temperature is decreased as the
outside temperature increases, according to a specific "compensation curve”.
With Sliding Temperature adjustment, the temperature set with the heating buttons (de-
tail 3 - fig. 1) becomes the maximum system delivery temperature. It is advisable to set
a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. Possible
adjustments can in any case be made by the user to improve comfort.
Compensation curve and curve offset
Press the
reset
button (detail 6 - fig. 1) for 5 seconds to access the "Sliding temperature"
menu; the display shows "CU" flashing.
Use the DHW buttons (detail 1 - fig. 1) to adjust the curve from 1 to 10 according to the
characteristic. By setting the curve to 0, sliding temperature adjustment is disabled.
Press the heating buttons (detail 3 - fig. 1) to access parallel curve offset; the display
shows "OF" flashing. Use the DHW buttons (detail 1 - fig. 1) to adjust the parallel curve
offset according to the characteristic (fig. 6).
Press the
reset
button (detail 6 - fig. 1) again for 5 seconds to exit the "Sliding Temper-
ature" menu.
If the room temperature is lower than the required value, it is advisable to set a higher
order curve and vice versa. Proceed by increasing or decreasing in steps of one and
check the result in the room.
fig. 6 - Example of compensation parallel curve offset
Adjustments from Remote Timer Control
A
If the Remote Timer Control (optional) is connected to the boiler, the above ad-
justments are managed according to that given in table 1.
Table. 1
System water pressure adjustment
The filling pressure with system cold, read on boiler water gauge (detail 17 - fig. 1), must
be approx. 1.0 bar. If the system pressure falls to values below minimum, the boiler stops
and fault
F37
is displayed. Operate the filling cock detail 1 - fig. 7 and bring it to the initial
value. Always close the filling cock at the end of the operation.
fig. 7 - Filling cock
3. INSTALLATION
3.1 General Instructions
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSON-
NEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL
MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF NA-
TIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.
3.2 Place of installation
This unit is an "open chamber" type and can only be installed and operated in perma-
nently ventilated rooms. An insufficient flow of combustion air to the boiler will affect its
normal operation and fume evacuation. Also, the fumes forming under these conditions
are extremely harmful to health if dispersed in the domestic environment.
If provided with the optional antiwind grille, the unit is suitable for operation in a partially
protected place in compliance with EN 297 pr A6, with min. temperature of -5°C. If
equipped with the special antifreeze kit it can be used with minimum temperature as low
as -15°C. The boiler must be installed under the slope of a roof, inside a balcony or in a
sheltered recess.
Therefore the place of installation must be free of dust, flammable materials or objects
or corrosive gases.
The boiler is arranged for wall mounting and c omes standard with a hooking bracket. Fix
the bracket to the wall according to the measurements given in the cover drawing and
hook the boiler on it. A metal template for marking the drilling points on the wall is avail-
able by request. The wall fixing must ensure a stable and effective support for the gen-
erator.
A
f the unit is enclosed in a cabinet or mounted alongside, a space must be pro-
vided for removing the casing and for normal maintenance operations.
I I I I
II
II
I
20
30
40
50
60
70
80
90
85
20
10
0
-10
-20
1
2
3
4
5
6
8
9
10
7
20
10
0
-10
-20
20
30
40
50
60
70
80
90
85
1
2
3
4
5
6
8
9
10
7
OFFSET = 20
OFFSET = 40
Heating temperature setting
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
DHW temperature adjustment
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Summer/Winter Switchover
Summer mode has priority over a possible Remote Timer Control
heating demand.
Eco/Comfort selection
On disabling DHW from the Remote Timer Control menu, the
boiler selects the Economy mode. In this condition, the
eco/com-
fort
button (detail 7 - fig. 1) on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the
boiler selects the Comfort mode. In this condition it is possible
select one of the two modes with the
eco/comfort
button (detail 7
- fig. 1) on the boiler panel.
Sliding Temperature
Both the Remote Timer Control and the boiler card manage Slid-
ing Temperature adjustment: the boiler card Sliding Temperature
has priority.
1
Содержание CLIZIA D 24 A
Страница 35: ......