4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdown (marked with the letter "
A
"): to restore
operation, press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to eliminate
the fault.
Faults marked with the letter "
F
" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
List of faults
Table. 2
5. TECHNICAL DATA AND CHARACTERISTICS
Table. 3 - Key of figures cap. 5
5.1 General view and main components
fig. 13 - General view CLIZIA D 24 A
Fault
code
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas flow to the boiler
and that the air has been eliminated
from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode and
that it is correctly positioned and free
of any deposits
Faulty gas valve
Check the gas valve and replace it if
necessary
Gas valve wiring disconnected
Check the wiring
Ignition power too low
Adjust the ignition power
A02
Flame present signal with
burner off
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
A03
Overtemperature protection
activation
Heating sensor damaged
Check the correct positioning and
operation of the heating sensor
No water circulation in the system Check the circulating pump
Air in the system
Vent the system
F04
Fume thermostat activated
(after activation of the fume
thermostat, boiler operation
is prevented for 20 minutes)
Fume thermostat contact open
Check the thermostat
Wiring disconnected
Check the wiring
Flue obstructed or not correctly
sized
Check the flue
F05
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
A06
No flame after the ignition
phase
Low pressure in the gas system
Check the gas pressure
Burner minimum pressure setting Check the pressures
F07
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
A09
Gas valve fault
Wiring disconnected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
A16
Gas valve fault
Wiring disconnected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
F20
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
A21
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
A23
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
A24
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
F34
Supply voltage under 180V. Electric mains trouble
Check the electrical system
F35
Faulty mains frequency
Electric mains trouble
Check the electrical system
F37
Incorrect system water pres-
sure
Pressure too low
Fill the system
Water pressure switch damaged or
not connected
Check the sensor
F39
External probe fault
Probe damaged or wiring shorted Check the wiring or replace the sensor
Probe disconnected after activat-
ing the sliding temperature
Reconnect the external sensor or disa-
ble the sliding temperature
A41
Sensor positioning
Delivery sensor or DHW sensor
detached from the pipe
Check the correct positioning and
operation of the sensors
F42
Heating sensor fault
Sensor damaged
Replace the sensor
F43
Exchanger protection trips.
No system H
2
O circulation
Check the circulating pump
Air in the system
Vent the system
F50
Gas valve fault
Modulating Operator wiring discon-
nected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
7
Gas inlet
44
Gas valve
8
DHW outlet
56
Expansion tank
9
Cold water inlet
72
Room thermostat (not supplied)
10
System delivery
74
System filling cock
11
System return
78
Anti-backflow device
14
Safety valve
81
Ignition and detection electrode
19
Combustion chamber
95
Diverter valve
22
Burner
114
Water pressure switch
27
Copper exchanger for heating and hot water
126
Fume thermostat
32
Heating circulating pump
138
External probe (not supplied)
36
Automatic air vent
139
Remote Timer Control (optional)
37
Cold water inlet filter
194
DHW water exchanger
38
Flow switch
241
Automatic bypass
39
Water flow limiter
278
Double sensor ( Heating)
42
DHW temperature sensor
290
Antiwind grille (optional)
44
32
114
36
14
19
27
81
95
278
42
38
37
10
8
7
9
11
194
39
74
22
126
78
56
290