casualty. The Non-professionals do not make the connection operation.
Warning
!
Before connecting PV array to the inverter, ensure the earth impedance between
PV array and ground is not less than 1Mohm.
Note
!
●
If there is more strings PV modules in parallel, each string PV module
should be with the same model, the same number of PV modules, the same
inclination angle, the same azimuth angle, and the same cross -sectional
area of the connecting wires.
●
Inspect every system carefully before installation.
Step 1: Follow the following steps to connect the DC side connector lead.
operating
instructions
Operation diagram
1. Loosen the
fastening nut of the
connector
。