13. 13 Analog output
The device has 1 passive analog output,
which can output a maximum current of 0 -
20 mA.
An external 24 V DC power adapter is re-
quired for operation.
20 mA
4 mA
230 V
Initial value
250 V
Final value
Fig.: Principle of the analog output with
voltage monitoring
The analog output can be configured in a
user-friendly way via the GridVis® software.
To do this, enter the assigned measurement
value, the initial and final value and the output
range in "
Periphery
."
Fig. Configuration of the analog output in the Grid-
Vis
®
software
Examples:
Assignment of effective power L1
(output range 4 - 20 mA)
20 mA
4 mA
500 W
Initial value
1000 W
Final value
• If the effective power is 500 W, a current of
4 mA is outputted via the analog output. At
an effective power of 1000 W, the output is
20 mA.
The measured effective power is directly
proportional to the current of the analog
output.
Assignment of the calculated effective power
factor cos
ϕ
(math.)
(output range 4 - 20 mA)
20 mA
4 mA
cos
ϕ
=
-1
Initial value
cos
ϕ
=
1
Final value
20 mA
0
• Monitoring of the effective power factor
cos
ϕ
(math.) with
cos
ϕ
(math.) > 0
effective power, consumed
cos
ϕ
(math.) < 0
effective power, delivered.