65
Technical specifications
Measured value
Measuring ranges (rng)
Resolution
Sinusoidal variables
Voltage L-N
0
1)
... 600 Vrms
0.01V
Voltage L-L
0
1)
... 1000 Vrms
0.01V
Current
0,001 ... 7.5 Arms
0.1 mA
Frequency of the fundamental
component
45 Hz..65 Hz
0.001 Hz
Measuring ranges
Current measurement
Power input
: approx 0.2 VA (Ri=5 mohm)
Nominal current
: 5A
Rated current
: 6A
Overload for 1 sec
: 100 A (sinusoidal)
Scanning frequency
: 20 kHz
Voltage measurement
Overvoltage category
: 300 V CAT III, 600 V CAT II
Impedance
: 4 MOhm/phase
Power input
: approx 0.1 VA
Scanning frequency
: 20 kHz
Transients
: >50 µs
Connectable conductors (current measurement and voltage measurement)
Solid core, multi-core, flexible core
: 0.08 - 4 mm2
Pin-end connector, wire end ferrules : 2.5 mm2, only one conductor may connected
per terminal connection.
1) The UMG604 can only determine measured values if a measurement-current voltage greater
than 10 Veff is applied to at least one voltage measurement input.