40
+
-
S2
S1
24V
=
4,4k
19
Digital
Input 1
3,9V
3,9V
20
21
Digital
Input 2
4,4k
+
-
24V
DC
Digital inputs
The UMG604 has 2 digital inputs to each of
which you can connect one transducer.
24 V version (optional)
An input signal is detected at a digital input if a
voltage of at least 10 V and maximum 28 V is
applied. In this case a current of at least 1 mA
and maximum 6 mA flows. Cables longer than
30 m must be laid with shielding.
Fig. 40.2 UMG604 with inputs for 24 V.
Example for the connection of external
switching contacts S1 and S2 to the digital
inputs 1 and 2.