71
Appendix
Default
Add Name
Setting range
Units setting
100 Automatically get TFTP configuration file
0 .. 9999
-
0
0 = switched off
x = file number
101 TFTP error handling
0 .. 1
-
0
0 = In the event of an error the
Configuration menu appears
in the UMG604.
1 = In the event of an error the
does NOT switch to the
Configuration menu of the UMG604.
110 Current transformer circuit (L1 .. L3)
0 .. 1
-
0
0 = three current transformers
1 = two current transformers (Aron circuit)
111 Voltage measurement system configuration
0 .. 1
-
0
0 = three-phase 4-conductor system
(TT, TN system)
1 = three-phase 3-conductor system
(IT system)