51
Configuration
Voltage measurement connection
options
The UMG604 recognises two connection
options for the voltage measurement.
Connection option 0
Direct measurement of the voltage in
•
3-phase 4-conductor systems.
Measurement via 3 voltage transformers
•
in 3-phase 4-conductor systems.
Connection option 1
Direct measurement of the voltage in
•
three-phase 3-conductor systems.
Measurement via 2 voltage transformers
•
(Aron circuit) in three-phase 3-conductor
systems.
Address Connection option
111
0 = Three-phase 4-conductor
systems (default factory
setting)
1 = three-phase 3-conductor
systems
Fig. 51.1 Section of the parameter list for the
voltage transformer connection options.