UMG 509-PRO
72
www.janitza.com
12. Commissioning
This section presents everything you need to
know about the initial commissioning of your
device
12.1 Supply voltage
Proceed as follows when applying the supply
voltage:
1.Connect the supply voltage with a terminal on
the back of the device.
2.After connecting the supply voltage, the first
measuring display, Home, appears on the dis-
play.
3.If no display appears, check whether the supply
voltage is within the nominal voltage range.
WARNING
Material damage due to disregard of the con-
nection instructions!
Voltages and currents outside the permissible
measuring range can destroy the device.
·
Comply with the measuring range specifica-
tions from the technical data.
·
Do not use the device for measuring DC
voltage.
INFORMATION
Before commissioning, delete any possible pro-
duction-related contents of the energy meters,
minimum and maximum values and recordings.
12.2 Measured voltage
Proceed as follows when connecting the mea-
sured voltage:
1.Connect the measured voltage with a terminal
on the back of the device.
2.After connecting the measured voltage, the
measured values displayed by the device for the
voltages L-N and L-L must match those at the
measurement input.
3.Take into account any voltage transformer fac-
tors that may be set.
WARNING
Risk of injury due to electrical voltage!
If the device is exposed to surge voltages above
the permissible overvoltage category, safety-rele-
vant areas of insulation in the device can be dam-
aged. This means that the safety of the product
can no longer be guaranteed.
Only use the device in environments in which
the permissible overvoltage category is not
exceeded.
Содержание UMG 509-PRO
Страница 23: ...23 UMG 509 PRO www janitza com...
Страница 27: ...27 UMG 509 PRO www janitza com...
Страница 47: ...47 UMG 509 PRO www janitza com...
Страница 94: ...UMG 509 PRO 94 www janitza com Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report...
Страница 95: ...95 UMG 509 PRO www janitza com Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot...
Страница 107: ...107 UMG 509 PRO www janitza com 15 8 Dimensional drawings Fig Side view Fig Bottom view...
Страница 115: ...115 UMG 509 PRO www janitza com...