UMG 509-PRO
60
www.janitza.com
Residual current transformer
When using the residual current inputs I5 and I6,
the corresponding transformer ratios of the resid-
ual current transformers used must be set.
Setting range:
Primary
1
..
1000000
Secondary
1
Factory default setting:
Primary
127
Secondary
1
This menu is also used to set the failure monitor-
ing of the corresponding residual current inputs:
·
Activated
- Switches on the failure monitoring
for the residual current measurement.
·
Deactivated
- Switches off the failure monitoring
for the residual current measurement.
Lock transformer ratios
Locking/unlocking of the current and voltage
transformer ratios can be done via the display.
The status can be read out via an internal device
address:
·If the entry "Lock all transformers" contains the
value "no", the registers are not locked (neither
current transformer (CT) nor voltage transformer
(VT) ratios).
·If the entry "Lock all converters" contains the
value "yes", the registers are locked
(CT and VT ratios).
Modbus
addr.
Value / Function
19716
Lock transformer ratios
0 = not locked
1 = locked
Fig. Lock transformer ratios
INFORMATION
·
A Modbus address list for your device can
be found in the download area at www.
janitza.com.
Fig. Configuration of residual current trans-
former
Fig. Configuring residual current measurement
monitoring
Содержание UMG 509-PRO
Страница 23: ...23 UMG 509 PRO www janitza com...
Страница 27: ...27 UMG 509 PRO www janitza com...
Страница 47: ...47 UMG 509 PRO www janitza com...
Страница 94: ...UMG 509 PRO 94 www janitza com Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report...
Страница 95: ...95 UMG 509 PRO www janitza com Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot...
Страница 107: ...107 UMG 509 PRO www janitza com 15 8 Dimensional drawings Fig Side view Fig Bottom view...
Страница 115: ...115 UMG 509 PRO www janitza com...