UMG 509-PRO
56
www.janitza.com
11.3 Measurement
In the Measurement menu, configure the follow-
ing:
·The transformers for current and voltage mea-
surement.
·The recording of transients.
·The recording of events.
·The mains frequency.
·The temperature sensor.
The device has:
·4 measurement channels for current measure-
ment (I1..I4)
·4 measurement channels for voltage measure-
ment (V1..V4 against Vref).
The measured voltages and measured currents
for measurement channels 1-4 must come from
the same network.
Fig. "Measurements" menu
11.3.1
Transformers
The following settings for main and auxiliary mea-
surements can be made here:
·Current transformer
·Voltage transformer
·Nominal current
·Nominal voltage
·Apply AUX / Main
- nominal voltage L-N, L-L
·Connection
As well as make settings for the ratios and moni-
toring for residual current transformers.
Current transformers
You can assign current transformer ratios to the
main measurement and the auxiliary measure-
ment respectively.
For direct measurement of currents, select the
5/5 A setting.
Setting range:
Primary
1 .. 1000000
Secondary
1 .. 5
Factory default setting:
Primary 5
Secondary
5
Fig. "Measurements" menu
Содержание UMG 509-PRO
Страница 23: ...23 UMG 509 PRO www janitza com...
Страница 27: ...27 UMG 509 PRO www janitza com...
Страница 47: ...47 UMG 509 PRO www janitza com...
Страница 94: ...UMG 509 PRO 94 www janitza com Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report...
Страница 95: ...95 UMG 509 PRO www janitza com Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot...
Страница 107: ...107 UMG 509 PRO www janitza com 15 8 Dimensional drawings Fig Side view Fig Bottom view...
Страница 115: ...115 UMG 509 PRO www janitza com...