UMG 509-PRO
58
www.janitza.com
Nominal voltage
The nominal voltage corresponds to the "Agreed
input voltage Udin" according to EN 61000-4-30.
The nominal voltage defines the reference point
for:
·Overdeviation (EN 61000-4-30)
·Underdeviation (EN 61000-4-30)
·Transients
·Events
·Automatic scaling of graphics.
·When the nominal voltage U
LN
is entered, the
nominal voltage U
LL
is calculated automatically.
Formula: U
LL
= U
LN
·
√
3
·When the nominal voltage U
LL
is entered, the
nominal voltage U
LN
is calculated automatically.
Formula: U
LN
=
U
LL
√
3
Setting range, U
LN
: 0 .. 999999 V
Setting range, U
LL
: 0 .. 999999 V
Factory default setting:
230 V (U
LN
),
398
V
(U
LL
)
You can also select the primary voltage as the
nominal voltage.
Apply L2 - L4
These settings are configurable per phase.
Under the menu item "Apply L2 - L4" you can
apply the settings from phase L1 to phases L2,
L3 and L4 respectively, so that you do not have to
enter everything again.
·
No
- The settings from phase L1 are not adopted
for phases L1 to L4.
·
Yes
- The settings from phase L1 are adopted
for phases L1-L4.
Fig. Transformer, main measurement
Fig. Apply settings for L2 - L4
Fig. "Apply settings" disabled.
Содержание UMG 509-PRO
Страница 23: ...23 UMG 509 PRO www janitza com...
Страница 27: ...27 UMG 509 PRO www janitza com...
Страница 47: ...47 UMG 509 PRO www janitza com...
Страница 94: ...UMG 509 PRO 94 www janitza com Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report...
Страница 95: ...95 UMG 509 PRO www janitza com Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot...
Страница 107: ...107 UMG 509 PRO www janitza com 15 8 Dimensional drawings Fig Side view Fig Bottom view...
Страница 115: ...115 UMG 509 PRO www janitza com...