40
RCM 202-AB
www.janitza.de
40
RCM 202-AB
12.2.3 Menu item: Monitoring active
Setting option:
Transformer monitoring activation
Shown on the dis-
play
Set values/control com-
mands
Remark
Monitoring
active
.
Monitoring activated
Monitoring deactivated
12.2.4 Menu items: Warning th. I to warning th. I AC50
Setting option:
Threshold values for the triggering of warning messages
A message appears if the set value is exceeded (display, Modbus, if parameterized:
digital output 1 and/or 2).
Shown on the dis-
play
Set values/control com-
mands
Remark
Warning th.
I
=
3.00
A 0.03
…
0.99 (steps of 0.01)
1.00
…
4.90 (steps of 0.1)
5.00
…
20.00 (steps of 1)
Total current with frequen-
cies up to 20
kHz (residual
current type B+)
Warning
th.
I
DC
=
3.00
A
Direct current
Warning
th.
I
AC2k
=
3.00
A
Alternating current with fre-
quencies up to 2
kHz (re-
sidual current type A)
Warning
th.
I
AC20k
=
3.00
A
Alternating current with fre-
quencies up to 20 kHz
Warning
th.
I
AC50
=
3.00
A
Fundamental oscillation
Warning
th.
I
2k
=
3.00
A
Total current with frequen-
cies up to 2
kHz (residual
current type B)