26
RCM 202-AB
www.janitza.de
26
RCM 202-AB
NOTE
The device address 1 and the baud rate of 19200 baud are factory-set.
If the RCM 202-AB is the first or last device in the Modbus line, the termina-
tion resistor must be set.
The ground terminals of all RS485 connections of multiple RCM 202-AB
must be connected with the ground wire of the cable. The ground wire must
be grounded in one point. The second wire pair of the bus cable is used as
the ground wire. Both wires of the pair are parallel connected.
The shield may be applied only on one side!
Terminate the first and last bus participants within a bus segment by pushing
the “Term” switch to the right.
NOTE
In the case of a RS485 connection from a control cabinet to a control cabi-
net, the Modbus connections B+ and A- must be electrically isolated.
Connect the current measurement transformer to the plug of the respective
current measurement input (I1 and I2). When doing so, observe the connec-
tions K and L (see also Tab. 3 on page 21).
Connect the analog and digital outputs if necessary.
Make sure that the connected connectors are still firmly seated.
Retighten all screw connections.
9.2 Commissioning
NOTE
The housing of the RCM 202-AB warms up during operation.
Connect the plug for the power supply to the N/L connection. The status LED
flashes green. RCM 202-AB initialization takes place. “I1
=
---” and “I2
=
---”
appear on the display.
Wait until initialization is completed. Initialization can take up to 60 seconds.
Initialization will take longer if the transformer measures residual currents
already during initialization.
The status LED lights up green and the measured values for the activated
measurement channels are shown on the display. The RCM 202-AB is
ready for operation.
If necessary, configure the RCM 202-AB (see chapter 12) according to the
system to be monitored and depending on the circuit of its connections.