44
RCM 202-AB
www.janitza.de
44
RCM 202-AB
Shown on the display Set values/control com-
mands
Remark
Factor 4-20mA = 20 A 5
A, 10
A, 15
A, 20
A
4
mA = 0
A measured total
current,
20
mA = max. 20
A meas-
ured total current (highest
vale = set value)
12.3 Menu: 3.Communication
NOTE
Parameterization mode must be released in order to display the menu
“3.Communication”.
Observe the user manual!
The annex to the user manual “Data and settings for the Modbus connec-
tion” must be strictly observed.
Fig. 22:
“3.Communication” menu
The menu items make it possible to set the following:
Communication interface RS485 (Modbus).
12.3.1 Menu item: Modbus active
ATTENTION
The RCM 202-AB is a Modbus slave. The communication interface must be
deactivated when the RCM 202-AB is not connected with a Modbus master.
Setting option:
Activation of the RS485 interface (Modbus)
Shown on the dis-
play
Set values/control com-
mands
Remark
Modbus active
.
Modbus activated
Modbus deactivated
3.Communication
Modbus
active
Address
=
1
Baud
rate
=
19200