14.1.1 The status LED is off
Text message:
None (display off, RCM 202-AB not ready for operation)
Cause:
Power supply interrupted or device defective
Remediation:
Check the plug for the power supply on the bus connections on the RCM 202-
AB for tight fit.
Check the power supply of the RCM 202-AB.
If necessary, replace the RCM 202-AB (see chapter 14.2 on page 58).
14.1.2 The status LED flashes green
Text message:
I1 = ---
and
I2 = ---
Cause:
Device initialization
Remediation:
NOTE
The initialization procedure can take multiple seconds.
Wait until the initialization procedure is completed.
14.1.3 The status LED lights up green
Text message:
None (display off)
Cause:
Device in sleep mode
Remediation:
Press any key.
Text message:
I1 = ---
or
I2 = ---
Cause:
Measurement channel deactivated
Remediation:
Check if the measurement channel is deactivated without a measured value
(menu item “Channel active” in menu “2.Channel parameter”).
Activate the channel if necessary.