62
RCM 202-AB
www.janitza.de
62
RCM 202-AB
Maximum current
350
mA
Start-up resistance
2
Ω
Maximum cable length
up to 30 m (32.8 yd) unshielded,
above 30
m (32.8 yd) shielded
RS485 interface
Protocol
Modbus RTU (RCM 202-AB as the slave)
Interface
RS485
Baud rate
Parameterizable, 9.6 … 115.2
kbaud
Address range
1 … 247
max. cable length (38.4
kbaud)
1200
m (1212.3 yd)
Cable (shielded, shield one-sided on PE)
Unitronic Li2YCY(TP) 2x2x0.22 (Lapp ca-
ble)
Termination resistor
120
Ω
(can be activated on the device)
Device safety
Safety regulations for electrical measurement, control, regulation and laboratory devices
Part 1: General requirements
IEC/EN 61010-1
Part 2-030: Particular requirements for
equipment having testing or measuring cir-
cuits
IEC/EN 61010-2-030
Electromagnetic compatibility (EMC)
Immunity from interference
Class A: Industrial sector
IEC/EN 61326-1
Electrostatic discharges
IEC/EN 61000-4-2
Voltage dips
IEC/EN 61000-4-11
Emissions
Class B: Residential sector
IEC/EN 61326-1
RFI field strength 30 ... 1000 MHz
IEC/CISPR11/EN 55011
Radiated interference voltage 0.15 ... 30
MHz
IEC/CISPR11/EN 55011
Standards
The RCM 202-AB fulfills the requirements according to
EN
62020:1998+A1:2005
(VDE
0663):2005
Ambient conditions
Ambient temperature during operation
-5 ... +55°C (23°F…131°F)
Ambient temperature during storage
-25 ... +70°C (-13°F…158°F)
Ambient temperature during transport
-25 ... +70°C (-13°F…158°F)