42
RCM 202-AB
www.janitza.de
42
RCM 202-AB
12.2.6 Menu item: Autom. reset
Setting option:
Activation of the automatic reset of warning and alarm mes-
sages after the end of the warning or alarm condition
Shown on the dis-
play
Set values/control com-
mands
Remark
Autom. reset
.
Automatic reset activated
Automatic reset deac-
tivated
12.2.7 Menu item: Hysteresis
ATTENTION
The hysteresis applies for all alarm thresholds of a channel and must always
be less than the lowest alarm threshold!
Setting option:
Threshold value for resetting the alarm messages
If the set value is fallen below, the message that the alarm threshold was exceeded
ends (display, Modbus, if parameterized: digital output 1 and/or 2).
Shown on the dis-
play
Set values/control com-
mands
Remark
Hysteresis = 0.00 A 0,00
…
1.00
A
in steps of 0.01
12.2.8 Menu item: Response delay
Setting option:
Time interval during which the exceedance of warning and
alarm thresholds is not reported
Shown on the dis-
play
Set values/control com-
mands
Remark
Response delay =
0.01
s
0.01
…
10.00
s
in steps of 0.01
12.2.9 Menu item: Reset delay
Setting option:
Time interval during which the warning and alarm messages re-
main active even though the warning thresholds or hysteresis
were already fallen below
Shown on the dis-
play
Set values/control com-
mands
Remark
Reset delay =
0.01
s
0.01
…
10.00
s
in steps of 0.01