background image

www.janitza.de

JPC 100-WEB

7

3. 

Product description

3. 2 

Intend use

 
The device is: 

• Intended for installation in control cabinets. 
• Not intended for installation in vehicles! 

Use of the device in non-stationary equip-
ment constitutes an exceptional environ-
mental condition and is only permissible 
by special agreement.

• Not intended for installation in environ-

ments with harmful oils, acids, gases, 
vapors, dusts, radiation, etc.

3. 1 

Scope of performance

The device is intended for:

• Visualization of current and voltage mea-

suring devices in bus systems.

• Measured value monitoring of connected 

Janitza measurement devices.

• Configuration of connected slave devices. 

You can connect up to 3 Janitza master 
devices and up to 30 Janitza slave devices to 
the JPC 100-WEB and manage them via the 
touchscreen. You can retrieve measured val-
ues from all integrated devices and configure 
slave devices. 

The slave devices are integrated either via 
the gateway function of the master de-
vices or directly via Modbus RTU with the 
JPC 100-WEB as the master device.

3. 4 

Incoming goods inspection

The prerequisites for trouble-free and safe 
operation of this device include proper trans-
port, storage, setup and assembly, as well as 
proper operation and maintenance. 

Exercise due caution when unpacking and 
packing the device, do not use force and only 
use suitable tools. 

Check the devices for flawless mechanical 
condition by visual inspection. 

Check the scope of delivery for complete-
ness before you start installing the device.

If it can be assumed that safe operation is no 
longer possible, the device must be taken out 
of operation immediately and secured against 
unintentional start-up. It can be assumed that 
safe operation is no longer possible if the 
device, for example:

• has visible damages, 
• no longer functions despite an intact pow-

er supply,

• was subjected to extended periods of un-

favorable conditions (e.g. storage outside 
of the permissible climate thresholds 
without adjustment to the room climate, 
condensation, etc.) or transport stress 
(e.g. falling from an elevated position, even 
without visible external damage, etc.).

Quantity Part. no.

Designation

1

15.06.358

JPC 100-WEB

1

33.03.381

Installation instruc-

tions

1

Mounting kit

1

12 V power supply

3. 5 

Scope of delivery

3. 3 

Operating concept

You can operate the device in the following 
ways:

• 

Directly on the device

 via the display with 

the touchscreen.

• Via the Ethernet interface with a connected 

PC

.

This operating manual only describes the 
operation of the device via the touchscreen.

ATTENTION

To be able to display the RCM values of the 
UMG509, the measurement device requires 
at least firmware 5.009. 

Содержание JPC 100-WEB

Страница 1: ...05 2020 Smart Energy Panel JPC 100 WEB User manual and technical specifications Janitza electronics GmbH Vor dem Polst ck 6 D 35633 Lahnau Support tel 49 6441 9642 22 Email info janitza de www janitza...

Страница 2: ...coming goods inspection 7 3 5 Scope of delivery 7 4 Mounting 8 4 1 Installation location 8 4 2 Mounting orientation 8 4 3 Securing 9 5 Installation 10 5 1 Disconnect switch 10 5 2 Supply voltage 10 5...

Страница 3: ...as a master device 23 9 2 Slave devices 24 9 2 1 Integrating a new slave device 25 9 2 2 Configuring the UMG 20 CM 25 9 3 Alarms and warnings 26 10 Service and maintenance 27 10 5 Remote access via T...

Страница 4: ...hts arising from them are the property of the respective own ers of these rights 1 3 Technical changes Make sure that your device matches the installation instructions First read and understand the do...

Страница 5: ...ing the user manual Read it before using the device Retain it for the entire service life of the product and keep it at hand ready for reference When using the device also observe the le gal and safet...

Страница 6: ...rdous voltage Consequently severe bodily injury or material damage can occur if they are not handled properly 2 3 Qualified personnel This device must be operated and main tained exclusively by qualif...

Страница 7: ...ation and maintenance Exercise due caution when unpacking and packing the device do not use force and only use suitable tools Check the devices for flawless mechanical condition by visual inspection C...

Страница 8: ...e JPC 100 WEB CAUTION Material damage due to disregard of the installation instructions Disregard of the installation instructions can damage or destroy your device Observe the information on the moun...

Страница 9: ...l lation cutout from the front 2 Insert the retaining brackets into the openings on the device provided for this purpose Fig 3 Inserting the retaining brackets 3 Push the retaining brackets towards th...

Страница 10: ...er supply Install the circuit breaker near the device and within easy reach of the user Mark the circuit breaker as the disconnect ing device for this measuring device 5 2 Supply voltage A supply volt...

Страница 11: ...page 24 1 Settings menu depending on the user role this menu is labeled Administrator Read only or Operator 2 Menu bar 3 Selected master device 4 Measured value overview of the selected master device...

Страница 12: ...view of the selected master device is displayed at this location Tabular measured value overview of the slave devices assigned to the selected master device in the lower area 6 2 Remote access To acce...

Страница 13: ...h areas 7 Settings 7 1 System Use the System tab to configure the basic settings of the JPC 100 WEB such as inter faces time setting or language The menu is divided into the areas Device Modbus TCP IP...

Страница 14: ...2 Use the Open File Explorer Fig 10 but ton to open the file system Fig 12 The Export device configuration pop up window Importing configuration To import a configuration file it must be avail able o...

Страница 15: ...ts in the IT network Consult your network administrator for the correct network settings for your device 7 1 3 TCP IP The TCP IP area shows the current IP ad dress and subnet mask of the JPC 100 WEB D...

Страница 16: ...you can perform the following actions by touching the corresponding entry Select between automatic and manual time and date setting Select between automatic and manual time zone Change the NTP server...

Страница 17: ...gged in This role allows viewing of measured values system settings and alarms Operator Standard role for logged in users They can also acknowledge and configure alarms and warnings as well as configu...

Страница 18: ...en the user management via the User Management button on the User settings tab In this case a new login with administrator access data is necessary Fig 21 User Management To change the username or pas...

Страница 19: ...requires access to a SMTP server to be able to send e mails You must define an interval at which JPC 100 WEB checks whether new warnings or alarms are present All new unacknowl edged warnings and alar...

Страница 20: ...ledge all alarms at once by pressing the Acknowledge All button or ac knowledge individual alarms by pressing the check mark after the corresponding alarm Use the Historic Alarms button to open a list...

Страница 21: ...devices in the JPC 100 WEB and to configure integrated devices Call Start page Configuration You must be logged in to the device as an administrator to configure measurement devices Use the tabs Maste...

Страница 22: ...measurement devices using Modbus RTU the master device JPC 100 WEB and slave devices must have the same baud rate The respective user information describes how to determine the baud rate of the respec...

Страница 23: ...Optional Activate deactivate the link to the device homepage in the measured value details Only for measurement devices with a device homepage 7 Save the configuration The master device is now displa...

Страница 24: ...you want to configure in the JPC 100 WEB You can switch between the different measure ment channels of the UMG 20 CM quickly using the arrow buttons Use this drop down menu to assign the slave de vic...

Страница 25: ...nimum maximum current mea surement values for all UMGs and to transfer the current configuration to all UMGs Use the Actions for this UMG button to reset ener gy meters and minimum maximum current mea...

Страница 26: ...enu to select which mea sured value is to be monitored Here you can configure the upper and lower limits for alarms and warnings for each measured value To facilitate selection the list of measured va...

Страница 27: ...and calibration Repairs and calibration can only be carried out by the manufacturer 10 3 Front panel foil The front panel foil can be cleaned with a soft cloth and standard household cleaning agents...

Страница 28: ...t s RS 485 Protocol Modbus RTU master 3 lead connection with GND B A Transmission rate1 9 6 kbps 19 2 kbps 38 4 kbps 57 6 kbps 115 2 kbps 230 4 kbps Display Type TFT color Diagonal 10 Resolution 1024...

Страница 29: ...31 Side view Fig 30 Rear view 282 mm 11 10 in 70 mm 2 76 in 184 mm 7 24 in 70 mm 2 76 in 35 mm 1 38 in 1 2 3 4 5 6 Fig 32 Bottom view 1 Ethernet 2 USB 2 0 type A 3 Micro USB 4 24 V supply voltage ter...

Отзывы: