Issue: 01.07.2020
Page 7
Installation
Quick Guide
–
Piping
Pipework:
Pipework sizing should be based on the total equivalent lengths, which includes equivalent lengths for bends, traps, risers etc. A
guide to sizing is noted below:
Expansion Valves:
Suitably selected externally equalized expansion valves are required for each evaporator. Fitting of the valves should be carried
out as follows:
➢
Carefully braze the TEV outlet to the 1/2
”
evaporator inlet pipe approximately 100mm from the distributor. Protect both
the TEV and distributor from excessive heat using a wet cloth.
➢
Connect the liquid line to the 3/8” TEV inlet
(preferably using a flare x solder adaptor). Ensure the correct size orifice is
fitted into the valve inlet before assembly and tightening.
➢
Make an equalization connection between the TEV and the suction line as per the TEV instructions.
➢
Fit the valve phial sensor to the suction line as per the TEV instructions once all brazing has been completed.
Solenoid Valve:
A suitably sized solenoid valve needs to be installed in the liquid line just before the TEV on single evaporator systems and just
before the ‘T’
piece in the main liquid line on Twin Systems (as shown on page 8). The liquid line solenoid valve is not supplied in
both Single and Twin system.
Liquid
Suction
Liquid
Suction
Liquid
Suction
3/8"
3/4"
3/8"
7/8"
3/8"
7/8"
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
1/2"
7/8"
1/2"
7/8"
1/2"
7/8"
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
1/2"
7/8"
1/2"
7/8"
1/2"
1 1/8"
(2x 3/8")
(2x 3/4")
(2x 3/8")
(2x 3/4")
(2x 3/8")
(2x 3/4")
- The pipe sizes indicated in brackets are from the ' T ' piece to each evaporator.
- Pipework should be selected on the total equivalent length of run between all units.
Condensing Unit
Model
Evaporator
Models
1x JCC2-80E
1x JCC2-80E
2x JCC2-60E
BSCU-40-M1/M3
10m
20m
30m
CellarPlus 90-T1/T3
BSCU-30-M1/M3
BSCU-35-M1/M3
BSCU-30-M1/M3
BSCU-35-M1/M3
CellarPlus 70-S1/S3
3/8"
7/8"
CellarPlus 70-T1/T3
2x JCC2-40E
3/8"
7/8"
CellarPlus 80-S1/S3
1/2"
7/8"
1/2"
System
- The pipe sizes indicated in
bold
are from condensing unit to ' T ' piece.
CellarPlus 80-T1/T3
7/8"
3/4"
3/8"
7/8"
2x JCC2-50E
Pipe Sizing: 10ºC Cellar R448A/R449A
1/2"
1x TE2-03
1x TE2-04
TEV Model
2x TE2-02
2x TE2-02
2x TE2-02
Содержание Cellar Plus 70-S1
Страница 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 07 2020 CELLAR COOLER RANGE TECHNICAL MANUAL...
Страница 8: ...Issue 01 07 2020 Page 8 Installation Quick Guide Piping Single System Twin System...
Страница 24: ...Issue 01 07 2020 Page 24 Drawings Dimensional drawings Indoor Unit 80E...
Страница 25: ...Issue 01 07 2020 Page 25 Drawings Dimensional drawings Outdoor Units BSCU 30 M1 M3 BSCU 35 M1 M3...
Страница 26: ...Issue 01 07 2020 Page 26 Drawings Dimensional drawings Outdoor Units BSCU 40 M1 M3...
Страница 28: ...Issue 01 07 2020 Page 28 Drawings Electrical wiring diagrams Outdoor BSCU 30 M1 BSCU 35 M1 BSCU 40 M1...
Страница 29: ...Issue 01 07 2020 Page 29 Drawings Electrical wiring diagrams Outdoor BSCU 30 M3 BSCU 35 M3 BSCU 40 M3...
Страница 33: ...Issue 01 07 2020 Page 33 Certification...
Страница 34: ...Issue 01 07 2020 Page 34 THIS PAGE IS LEFT BLANK INTENTIONALLY...