background image

 

Issue: 01.07.2020 

 

 

Page 18  

Commissioning 

 

 

Pre startup checks 

 

Before starting the condensing unit, the following checks should be carried out as a minimum: 
 

 

Check electrical supply is correct and all connections are sound. 

 

All moving parts are free and guards fitted. 

 

Compressor oil level satisfactory. 

 

Initial settings for safety switches. 

 

Overload set correctly.  

 

All valves in correct operating position. 

 

Initial refrigerant charge. 

 

Gauge manifold connected to both low and high sides of system. 

 

 

Running the unit 

 

 

Run the unit and check compressor and condenser fan operation. 

 

Check  system  pressures  and  temperatures,  gas  charge  and  running  currents  of  motors  to  ensure  correct 
operation. 

 

Check compressor suction superheat. This should be between 10K and 20K at normal operating conditions. 

 

Final adjustment of safety switch settings. 

 

Allow the system to run for 3 

 4 hours. Check compressor oil level and top up with the correct oil type as 

required (RL32-3MAF). Recheck the compressor oil level again after 24 hours operation. 

 

Carry out final leak test and ensure all panels/covers are fitted and screws tightened. 

 

Log all information along with the system model and serial numbers for future reference. 

 

Ensure  that  the  customer  /  responsible  person  is  provided  with  basic  operating  instructions  and  where 
electrical isolators are situated in case of emergency. 

 

Compressor operation 

 

Scroll  compressor  motors  are  designed  to  run  only  in  one  direction.

  This  is  not  an  issue  with  single  phase 

compressors as they will always run in the correct direction. The correct rotation of a three-phase compressor motor 
depends on the connection of the three incoming phases to the unit. Correct rotation can be determined by a drop in 
suction pressure and a rise  in discharge  pressure when the compressor is energized. Running the compressor for a 
short period of time in reverse direction will have no negative impact but prolonged running in reverse direction may 
cause  premature  failure. 

To  reverse the  rotation of a  three-phase  scroll  compressor,  shut off the incoming power 

supply to the unit, swap connection of any two of the three incoming phases at the unit isolator, reapply power to 
the unit and following compressor restart, recheck operating pressures. 

 

Do not operate scroll compressors in a vacuum condition, as this will cause the scrolls to overheat very quickly 
causing premature failure. 

 

Ensure an adequate liquid charge has been introduced to the high side of the system before starting to ensure a 
minimum operating pressure on the suction side of 0.5 bar is maintained, otherwise overheating of the scrolls and 
subsequent damage may occur. 

 

 

Содержание Cellar Plus 70-S1

Страница 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 07 2020 CELLAR COOLER RANGE TECHNICAL MANUAL...

Страница 2: ...ctrical 16 Commissioning General 17 Pre startup checks running the unit compressor operation 18 Vacuum Operation 19 Safety pressure switch setting 19 High pressure safety 19 Low pressure safety 19 Com...

Страница 3: ...r Housed condensing units Copeland scroll compressor Basic control box Adjustable LP HP switch fitted Drier sight glass fitted Acoustic insulation General Single Twin Evaporator systems Cellar tempera...

Страница 4: ...ystem COP 3350 1 2 5 8 1 2 3 4 1 2 3 4 7 94 Nominal Capacity 1 kW 1x JCC2 80E 2x JCC2 40E 2x JCC2 60E 1x JCC2 80E 34 36 34 2765 2x 2560 1 2 5 8 4250 3350 36 41 1 2 3 4 2x 2680 4070 4070 2x 2270 10 10...

Страница 5: ...2 0 12 2 25 BSCU 30 M3 400 3 50 10 3 40 0 5 1 16 BSCU 35 M1 230 1 50 25 0 97 0 14 0 32 BSCU 35 M3 400 3 50 9 0 46 0 5 7 20 BSCU 30 M1 230 1 50 21 5 82 0 13 3 25 BSCU 30 M3 400 3 50 10 3 40 0 5 4 16 BS...

Страница 6: ...ds which may cause severe injury or death Disconnect and shut off power before installation or service of the equipment Refrigerant release into the atmosphere is illegal Proper evacuation recovery ha...

Страница 7: ...ized solenoid valve needs to be installed in the liquid line just before the TEV on single evaporator systems and just before the T piece in the main liquid line on Twin Systems as shown on page 8 The...

Страница 8: ...Issue 01 07 2020 Page 8 Installation Quick Guide Piping Single System Twin System...

Страница 9: ...ction Twin The JCC evaporators come pre fitted with an electronic controller as standard For the Twin Systems one of the evaporators needs to be designated as the Lead Unit with the other being the La...

Страница 10: ...n and distribute plenty of air thus lowering the condensing temperature To optimize the unit running conditions the condenser coil must be cleaned at regular intervals The evaporators can be mounted d...

Страница 11: ...Installation Installation clearances The installation location should allow sufficient space for air flow and maintenance around the units Outdoor Indoor 500mm 500mm 1500mm to any obstruction Minimum...

Страница 12: ...ng of the unit when brazing connections Install insulation with a minimum wall thickness of 1 2 on all suction lines Adequately support all pipe work at a maximum of 2 metre intervals Use of incorrect...

Страница 13: ...he area surrounding the system is safe inform relevant personnel and fit warning signs indicating high pressure testing Also use correct PPE as required Listen for any possible leaks and check all joi...

Страница 14: ...isture is suspected Once the system is isolated and the vacuum pump is switched off any rise in pressure indicates that either there may be a leak in the system or moisture is still present In this ca...

Страница 15: ...in from the indoor unit is 20mm or 3 4 This can be either copper or plastic Flexible hose is not recommended as it can easily kink causing a blockage and water to back up in the unit Important Note Th...

Страница 16: ...n access to the electrical box on the outdoor unit remove the screws of the panel located on the right hand side of the unit and remove the panel The electrical box is located behind the panel Importa...

Страница 17: ...period is adequate to clear any frost build up on the evaporator coil Carry out final leak test and ensure all covers are fitted and securing screws are tightened Log all information along with syste...

Страница 18: ...responsible person is provided with basic operating instructions and where electrical isolators are situated in case of emergency Compressor operation Scroll compressor motors are designed to run onl...

Страница 19: ...e high pressure switch can be set to lower values depending on the ambient conditions Low pressure safety The low pressure safety switch protects the compressor against deep vacuum operation a potenti...

Страница 20: ...icated and factory sealed so no maintenance is necessary 3 Condenser Evaporator Coils Clean and inspect at regular intervals Check and remove the dirt and debris between the fins using a soft brush an...

Страница 21: ...e installer or local authority for more information Batteries must be removed from the controller and disposed of separately in accordance with relevant local and national legislation 8 Component repl...

Страница 22: ...leak testing requirements are as follows OLD LEGISLATION NEW LEGISLATION LEAK CHECKING FREQUENCY 3 30 kgs 5 50 TCO Eq Every 12 months but can be increased to 24 months if fitted with a fixed leak det...

Страница 23: ...Issue 01 07 2020 Page 23 Drawings Dimensional drawings Indoor Units 40E Dimensional drawings Indoor Units 50E 60E...

Страница 24: ...Issue 01 07 2020 Page 24 Drawings Dimensional drawings Indoor Unit 80E...

Страница 25: ...Issue 01 07 2020 Page 25 Drawings Dimensional drawings Outdoor Units BSCU 30 M1 M3 BSCU 35 M1 M3...

Страница 26: ...Issue 01 07 2020 Page 26 Drawings Dimensional drawings Outdoor Units BSCU 40 M1 M3...

Страница 27: ...Issue 01 07 2020 Page 27 Drawings Electrical wiring diagrams Indoor Indoor JCC2 40E 50E 60E JCC2 80E Indoor Lead Lag Twin...

Страница 28: ...Issue 01 07 2020 Page 28 Drawings Electrical wiring diagrams Outdoor BSCU 30 M1 BSCU 35 M1 BSCU 40 M1...

Страница 29: ...Issue 01 07 2020 Page 29 Drawings Electrical wiring diagrams Outdoor BSCU 30 M3 BSCU 35 M3 BSCU 40 M3...

Страница 30: ...the programming mode by pressing the SET and the buttons together for more than 3 seconds C or F LED starts blinking The first parameter Hy is displayed Press the SET button to display the parameter v...

Страница 31: ...alarm condition and its signalling With iF do it represents the delay to activate the door open alarm 0 99 minutes 5 5 LS Minimum Set Point 55 C 67 F 55 C 55 F 4 C US Maximum Set Point 99 C 210 F 99 C...

Страница 32: ...after setting Low pressure side Range Turning the range adjusting screw 2 clockwise will decrease the cut in pressure setting Turning the range adjusting screw anti clockwise will increase the cut in...

Страница 33: ...Issue 01 07 2020 Page 33 Certification...

Страница 34: ...Issue 01 07 2020 Page 34 THIS PAGE IS LEFT BLANK INTENTIONALLY...

Страница 35: ...J E Hall Limited Hansard Gate West Meadows Derby DE21 6JN England Tel 44 0 1332 253400 Fax 44 0 1332 371061 Email helpline jehall co uk www jehall com Issue 01 07 2020...

Отзывы: