Issue: 01.07.2020
Page 31
Technical Information
Controller parameters
Label
Description
Range
Default setting
JEH Setting
Hy
Differential
0.1 ~ 25°C / 1 ~ 45°F
2.0°C / 4°F
2.0°C
ot
Probe calibration
-9.9 ~ 9.9°C / -18 ~ 18°F
0.0
0.0
AC
Anti Short Cycle Delay
0 ~ 50 minutes
1
3
CH
Kind of Action (Cool / Heat)
cL ~ Ht
cL
cL
rE
Resolution (°C only): dE = decimal between -9.9 ~ 9.9°C; in = integer
dE ~ in
dE
in
id
Interval between defrost cycles
0 ~ 99 hours
8
6
Md
Maximum defrost length
0 ~ 99 minutes
20
30
AU
Maximum Alarm Temperature
~ 99°C / ~210°F
99°C / 99°F
99°C
AL
Minimum Alarm Temperature
-55°C / -67°F
-55°C / -55°F
-55°C
iP
Digital input polarity: oP = activated by closing the contact; cL = activated by opening the contact
cL ~ oP
cL
cL
iF
Digital input configuration: EA = external alarm; EA message is displayed: bA = serious alarm; CA
message is displayed: do = door switch function: dF = defrost activation: Au = not used: Hc =
inversion of the kind of action
EA / bA / do / dF / Au / db
/ Hc
EA
EA
di
Digital input delay. With iF = EL or bA delay between the detection of the external alarm condition
and its signalling. With iF = do it represents the delay to activate the door open alarm
0 ~ 99 minutes
5
5
LS
Minimum Set Point
-55°C / -67°F
-55°C / -55°F
4°C
US
Maximum Set Point
99°C / 210°F
99°C / 99°F
16°C
od
Output activation delay at startup
0 ~ 99 minutes
0
0
Cy
Compressor on time faulty probe. Cy = 0 compressor always OFF
0 ~ 99 minutes
15
5
Cn
Compressor off time faulty probe. Cn = 0 compressor always active
0 ~ 99 minutes
30
10
CF
Measurement units: °C = Celsius; °F = Fahrenheit
°C / °F
°C
°C
dY
Display delay
0 ~ 15 minutes
0
0
dF
Display during defrost: rt = real temperature; it = start defrost temperature: St = SET POINT: dF =
label dF
rt / it / St / dF
it
it
Ad
Temperature alarm delay
0 ~ 99 minutes
15
15
dA
Exclusion of temperature alarm at startup
0 ~ 99 minutes
90
90
dC
Compressor and fan status when door open: no = normal; Fn = Fans OFF; cP = Compressor OFF; Fc
= Compressor and fans OFF
no / Fn / cP / Fc
no
no
rd
Regulation with door open: n = no regulation if door is opened; Y = when di is elapsed regulation
restarts even if door open alarm is present
n ~ Y
Y
Y
Pt
Parameter code table
Read Only
-
-
rL
Firmware release
Read Only
-
-
Parameter Menu (selected parameters)
Hidden Parameter Menu (Full list including above parameters)
Dixell XR02CX Parameters
Содержание Cellar Plus 70-S1
Страница 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 07 2020 CELLAR COOLER RANGE TECHNICAL MANUAL...
Страница 8: ...Issue 01 07 2020 Page 8 Installation Quick Guide Piping Single System Twin System...
Страница 24: ...Issue 01 07 2020 Page 24 Drawings Dimensional drawings Indoor Unit 80E...
Страница 25: ...Issue 01 07 2020 Page 25 Drawings Dimensional drawings Outdoor Units BSCU 30 M1 M3 BSCU 35 M1 M3...
Страница 26: ...Issue 01 07 2020 Page 26 Drawings Dimensional drawings Outdoor Units BSCU 40 M1 M3...
Страница 28: ...Issue 01 07 2020 Page 28 Drawings Electrical wiring diagrams Outdoor BSCU 30 M1 BSCU 35 M1 BSCU 40 M1...
Страница 29: ...Issue 01 07 2020 Page 29 Drawings Electrical wiring diagrams Outdoor BSCU 30 M3 BSCU 35 M3 BSCU 40 M3...
Страница 33: ...Issue 01 07 2020 Page 33 Certification...
Страница 34: ...Issue 01 07 2020 Page 34 THIS PAGE IS LEFT BLANK INTENTIONALLY...