Issue: 01.07.2020
Page 21
Service & Maintenance
7. Unit decommissioning and disposal
•
At the end of the system’s useful life, a suitably qualified engineer should decommission it. The refrigerant and
compressor oil are classed as hazardous waste and as such must be reclaimed and disposed of in the correct manner,
including completion of waste transfer paperwork. The system components must be disposed of or recycled as
appropriate in the correct manner.
NOTICE
Disposal requirement
Your refrigeration product is marked with this symbol. This means that electrical and electronic
products shall not be mixed with unsorted household waste. Do not try to dismantle the system
yourself: the dismantling of the refrigeration system, treatment of the refrigerant, of oil and of
other parts must be done by a qualified installer in accordance with relevant local and national
legislation. Refrigeration equipment must be treated at a specialized treatment facility for re-use,
recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent
potential negative consequences for the environment and human health. Please contact the
installer or local authority for more information.
Batteries must be removed from the controller and disposed of separately in accordance with
relevant local and national legislation.
8. Component replacement (connections tightening torque value)
•
Torque tightening value of all the components and compressor connections can be refer to the table below:
Torque tightening values
9. Warranty
•
The warranty as provided by J & E Hall on its products is subject to correct application, siting and installation procedures
together with subsequent recorded maintenance/servicing carried out in accordance with our recommendations. Failure
to do so could result in the withdrawal of our warranty. Please go to our website for our detailed warranty terms and
conditions: www.jehall.co.uk
Liquid
Suction
Main Cap
Main Cap
Hexagonal Cap
BSCU-30-M1
ZB21 KQE-PFJ-558
BSCU-30-M3
ZB21 KQE-TFD-558
BSCU-35-M1
ZB26 KQE-PFJ-558
BSCU-35-M3
ZB26 KQE-TFD-558
BSCU-40-M1
ZB29 KQE-PFJ-558
BSCU-40-M3
ZB29 KQE-TFD-558
-
-
-
-
-
7/16" - 20UNF
(14-16 Nm)
M
e
d
iu
m
T
e
m
p
e
ra
tu
re
Rotolock (Discharge)
Thread:
Toghtening Torque
(Nm)
Not Applicable (Brazed Connection)
Model
Thread/Size:
Shrader Valve 1/4"
SAE, Gomex Hose and
HL Pressure Switch
Service Valves
Se
ri
e
s
COMPRESSOR
Rotolock (Suction)
Thread:
Tightening Torque
(Nm)
REMARKS
2
M25*1.0mm
(42-47 Nm)
M33*1.5mm
(42-47Nm)
M16*1.0mm
(20-25 Nm)
3
M18*1.0mm
(25-30 Nm)
Содержание Cellar Plus 70-S1
Страница 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 07 2020 CELLAR COOLER RANGE TECHNICAL MANUAL...
Страница 8: ...Issue 01 07 2020 Page 8 Installation Quick Guide Piping Single System Twin System...
Страница 24: ...Issue 01 07 2020 Page 24 Drawings Dimensional drawings Indoor Unit 80E...
Страница 25: ...Issue 01 07 2020 Page 25 Drawings Dimensional drawings Outdoor Units BSCU 30 M1 M3 BSCU 35 M1 M3...
Страница 26: ...Issue 01 07 2020 Page 26 Drawings Dimensional drawings Outdoor Units BSCU 40 M1 M3...
Страница 28: ...Issue 01 07 2020 Page 28 Drawings Electrical wiring diagrams Outdoor BSCU 30 M1 BSCU 35 M1 BSCU 40 M1...
Страница 29: ...Issue 01 07 2020 Page 29 Drawings Electrical wiring diagrams Outdoor BSCU 30 M3 BSCU 35 M3 BSCU 40 M3...
Страница 33: ...Issue 01 07 2020 Page 33 Certification...
Страница 34: ...Issue 01 07 2020 Page 34 THIS PAGE IS LEFT BLANK INTENTIONALLY...