Drain
indoors
Water seal
The condensation water is lead to an indoor drain
(subject to local rules and regulations).
Route the pipe downward from
JAMA Inverter
.
The condensation water pipe must have a water seal to
prevent air circulation in the pipe.
Gutter
drainage
Frostfritt
djup
LEK
Frost proof depth
Water seal
The outlet of the condensation water pipe must be at frost
free depth.
Route the pipe downward from
JAMA Inverter
.
The condensation water pipe must have a water seal to
prevent air circulation in the pipe.
Installation area
The distance between
JAMA Inverter
and the house wall
must be at least 150 mm. Clearance in front of
JAMA
Inverter
should be at least one metre.
3000 mm
400 mm
Minimalt
fritt utrymme
Minimalt
fritt utrymme
Fritt utrymme
framför
150 mm
Fritt
utrymme
bakom
600mm
Minimum
free space
Minimum
free space
Free
space
behind
400 mm
600 mm
150 mm
3000 mm
Free space
in front
Supplied components
LEK
Particle filter R25 (HQ1).
2 flexible hoses (R25) with 4
seals
Chapter 2 |
Delivery and handling
8
Содержание M8
Страница 1: ...Installer manual LEK LEK LEK J M Inverter M8 M12 M16 Air water heat pump...
Страница 2: ......
Страница 16: ...LEK DATA XL2 UB1 UB2 XL1 UB3 W1 LEK DATA PF3 PF1 Chapter 3 The heat pump design 14...
Страница 47: ...Electrical circuit diagram JAMA Inverter M8 Chapter 9 Technical data 46 Kaukora Oy...
Страница 49: ...JAMA Inverter 12 Chapter 9 Technical data 48 Kaukora Oy...
Страница 51: ...JAMA Inverter 16 Chapter 9 Technical data 50 Kaukora Oy...
Страница 54: ......
Страница 55: ...Kaukora Oy PL 21 Tuotekatu 11 21200 Raisio Puh 02 4374 600 E mail kaukora kaukora fi www kaukora fi...