External heating cable KVR 10 (Accessory)
JAMA Inverter
is equipped with a plinth for external
heating cable EB14 not supplied). The connection is fused
with 250 mA (F3 on the communication board AA23). If
another cable is to be used, the fuse must be replaced
with a suitable one (see table).
NOTE
Self regulating heating cables must not be
connected.
Fuse (F3)
Total
power
(W)
Length
(m)
T100mA/250V
15
1
T250mA/250V
45
3
T500mA/250V
90
6
*
Fitted at the factory
.
Connect external heating cable (EB14) to terminal block
X1:4–6 according to following image:
56
4
23
1
([WHUQDO
JAMA Inverter
;
(%
([WHUQDO KHDW FDEOH
$$
)
NOTE
The pipe must be able to withstand the heat
from the heating cable.
To ensure this function the accessory KVR 10
should be used.
Cable
routing
The following images show recommended cable rout-ing
from the distribution box to the condensation water pipe.
Route the heating cable (EB14) through the grommet
underneath and secure with two cable ties at the electrical
connection. Transfer between electrical cable and heating
cable must occur after the lead-in to the condensation
water pipe.
JAMA Inverter M
8
LEK
Heating cable (EB14)
Secure the heating
cable (EB14) here
using two cable ties.
Chapter
5
|
Electrical
connections
28
Содержание M8
Страница 1: ...Installer manual LEK LEK LEK J M Inverter M8 M12 M16 Air water heat pump...
Страница 2: ......
Страница 16: ...LEK DATA XL2 UB1 UB2 XL1 UB3 W1 LEK DATA PF3 PF1 Chapter 3 The heat pump design 14...
Страница 47: ...Electrical circuit diagram JAMA Inverter M8 Chapter 9 Technical data 46 Kaukora Oy...
Страница 49: ...JAMA Inverter 12 Chapter 9 Technical data 48 Kaukora Oy...
Страница 51: ...JAMA Inverter 16 Chapter 9 Technical data 50 Kaukora Oy...
Страница 54: ......
Страница 55: ...Kaukora Oy PL 21 Tuotekatu 11 21200 Raisio Puh 02 4374 600 E mail kaukora kaukora fi www kaukora fi...