Manual
JAKKA Control Kit 4
7
www.jakkagroup.com
nr
Read
Write
bits
Parameter
Default
Range
0
0-1
0
0-4
1
1-3
1.1
R/W
7
Run
1.1
R/W
6-4
Operation Modes, fan, heat, cool, auto,VOD
1.1
R/W
3-2
Exhaust fan speed (low,med,high)
1.1
R/W
1-0
Supply fan speed (low,med,high)
1
1-3
Reserved
-
1.2
R/W
7
1.2
R/W
6
Master
0
0-1
1.2
R
5
By-pass
0
0-1
1.2
R/W
4-0
Set point + 1
16
16-32
2.3
R/W
7-0
filter time(1 = 10 min)
12
0-2550
2.4
R/W
7-6
Reserved
-
2.4
R/W
5
Set clock with on time
0
0-1
2.4
R/W
4
Reserved
-
2.4
R/W
3
block 1 or 2
0
0-1
2.4
R/W
2-0
day 1-7 **
1
1-7
-1
--.--,0-23
3.5
R/W
7-0
On time in hours
3.6
R/W
7-0
On time in minutes
-1
--.--,0-59
-1
--.--,0-23
4.7
R/W
7-0
Off time in hours
4.8
R/W
7-0
Off time in minutes
-1
--.--,0-59
5.9
R
7
Write disable
0
0-1
5.9
R
6-0
Errors
0
0-126
5.A
R
7-0
Temp
-
-30-80
(*)
Depending on the type of Modbus software used, the holding register addressing range starts either at 0x0000 or at 0x0001. If
your Modbus software starts addressing from 0x0000 you can use the holding register addresses shown in the table above. If your
Modbus software addressing range starts at 0x0001 then add 1 to the holding register addresses listed in the table above.
This is also true for the various test tools available for Modbus…
Tabdial32 starts at 0x0000. (
http://www.leroy-automation.com/free%20softwares.html
) The Tabdial32 tool does not
support the write single holding register command.
Modbus Tester (
http://www.modbus.pl/downloads.htm
) starts at 0x0001.
(**) If 2.4 byte is written the Remote control writes the 3 and 4 nr bytes also in his memory of the display.
2.4.1
Convert table for Lennox
CAS
Holding
register
Access
Heat recovery Unit Basic
Parameter name
Conversion
Range
R
W
101
100
0064
X
102
101
0065
X
103
102
0066
X
X
104
103
0067
X
X
105
104
0068
X
106
105
0069
X
107
106
006A
X
X
108
107
006B
X
X
V
109
108
006C
X
X
V
110
109
006D
X
X
V
111
110
006E
X
112
111
006F
X
V
113
112
0070
X
V
114
113
0071
X
115
114
0072
X
116
115
0073
X
117
116
0074
X
118
117
0075
X
X
119
118
0076
X
X
120
119
0077
X
X
121
120
0078
X
X
V
122
121
0079
X
X
V
123
122
007A
X
X
V
124
123
007B
X
X
V
Bit0: °C / °F, Bit1: bar / psi
Reserved (186)
Stop, Run
No/Yes
See error list
reserved
Operation Modes: fan, heat, cool, auto, VOD
16 - 32 °C
Low, Med, High(1,2,3)
Low, Med, High(1,2,3)
-+xxx.xx / 100
-+xxx.xx / 100
-+xxx.xx / 100
Output 0 -1
Output 0 - 1
Output 0 - 1
0..100%
x10 minutes
0-1
1-7 (Monday = 1)
--.--, 00 – 23 hours
--.--, 00 – 59 minutes
--.--, 00 – 23 hours
--.--, 00 – 59 minutes
..
..
..
200
199
00C7
Modbus Units
Device type
State
Master is Modbus
Error Code
Warning Code
Status
Set point
Fan speed Exhaust
Fan speed Supply
Room Temperature
Indoor sensor
Outdoor sensor
BMS
BMS unit
Season
Bypass Valve (relay)
Filter time
Block 1 or 2
Day 1-7
On time in hours
On time in minutes
Off time in hours
Off time in minutes
reserved
reserved