JAKKA Control Kit 4
Manual
www.jakkagroup.com
28
6.3
Connector description
Connector
Pin
Pin Description
J2
(Stelvio, BS95/4A + CT84)
(Stocko, MKF 2800 series)
1
2
3
Earth
230V neutral
230V phase
Mains input
The control is equipped with one fuse, in the phase. The
fuse-holder is appropriate for glass fusses of 5x20 mm. The
control is default equipped with one TBD slow fuse. This
value may be lowered.
The mains cable must be at least 3x0.75mm
2
Connector
Pin
Pin Description
J4
(Stelvio, BS95/4A + CT84)
(Stocko, MKF 2800 series)
1
2
3
Earth
Supply fan 230V
Supply fan Neutral
Supply fan
Fan
Triac output, max output is 480W
Maximal cable length is 1 meter
Connector
Pin
Pin Description
J5
(Molex, Minifit Jr. 5557 2x8
receptacle with terminals 5556)
9-1
10-2
11-3
12-4
13-5
14-6
15-7
16-8
Season select input
Remote Control (Senso Argus Link)
High Limit Switch 110°C
Heating Control Switch 70°C
BMS (on/off) input
BMS unit (on/off) input
Indoor Sensor (NTC)
Outdoor sensor (NTC)
Sensor input
All these sensor inputs carry a voltage of 5 V. The maximum
cable length is 1 meter.
The sensors connected to the control should be free from the
appliance earth.
All NTC's have a resistance of 12k@25°C β=3740.
Temp-range NTC is -10°C to 118 °C
Connector
Pin
Pin Description
J6
(Stelvio, BS95/3A + CT84)
(Stocko, MKF 2800 series)
1
2
3
230V Bypass valve open
230V Bypass valve close (optional)
230V Common Neutral
Bypass valve
Usable output current is 0,5A, cos φ = 0.7.
Maximal cable length is 1 meter
Connector
Pin
Pin Description
J7
(Stelvio, BS95/5A + CT84)
(Stocko, MKF 2800 series)
1
2-3
4-5
Common Protective Earth (PE)
Normal operation OK output (NO)
Potential free
Alarm output (NC)
Potential free
BMS status output
Usable output current is TBD.
Maximal cable length is TBD meter