JAKKA Control Kit 4
Manual
www.jakkagroup.com
10
2.4.5
Example Read
nr
Read
Write
bits
Parameter
Default
Range
5
.9
R
7
W
rite disable
0
0-1
5
.9
R
6-0
E
rrors
0
0-126
5
.A
R
7-0
T
emp
-
-30-80
2.4.6
Example Write
nr
Read
Write
bits
Parameter
Default
Range
0
0-1
0
0-5
1
1-3
1
.1
R/W
7
R
un
1
.1
R/W
6-4
O
peration Modes, fan, heat, cool, auto,VOD
1
.1
R/W
3-2
E
xhaust fan speed (low,med,high)
1
.1
R/W
1-0
S
upply fan speed (low,med,high)
1
1-3
reserved
-
1
.2
R/W
7
1
.2
R/W
6
M
aster is Modbus
0
0-1
1
.2
R
5
B
y-pass
0
0-1
1
.2
R/W
4-0
S
et point
16
16-32
Bytes Description Bits
01
# slave
0000.0001
03
00
00
commando
0000.0003
start addr H 0000.0000
start addr L
0000.0005
00
# data H
W
EEE.EEEE
01
# data L
TTTT.TTTT
??
Checksum H
??
Checksum L
Bytes Description Bits
01
# slave
0000.0001
06
00
01
commando
0000.0006
start addr H 0000.0000
start addr L
0000.0001
00
# data H
R
OOO.
EE
SS
00
# data L
r
M
B
S.SSSS
??
Checksum H
??
Checksum L
2.5
System set-up
2.5.1
Fan speeds
The control works with two different types of min/max limits:
1.
Absolute fan speed min/max settings
Settings are factory set and cannot be changed. The fans are always operating within these
limits
2. VOD fan min/max settings
These min/max settings are applicable when the unit works in VOD mode, but are always
within the absolute
limits (no. 1). The limits will be corrected with the fan balancing offset
(§ 2.5.2) if not zero.
2.5.2
Fan balancing
Fan balancing can be used to adjust the supply and exhaust air ratio. This can be done by changing
the parameter
offset
_
supply_exhaust_air.
In case of a negative offset the exhaust fan speed is below the supply fan speed
In case of a positive offset the exhaust fan speed is above the supply fan speed.
When the offset is 0 the exhaust and supply fan speed is equal.