Functional description
5.2.3 CAN-Bus settings [CANBus1] / [CANBus2]
5.2.3.1 [BaudRate]
There are three possibilities for setting the baudrate.
1. Automatic baudrate detection (BaudRate=Auto):
The status diagram (Fig. 4-1) shows the function of the automatic baudrate
detection.
Note: The baudrate can only be detected if there is bus traffic and at least
two nodes per segment are active.
Listen to CAN
0/1
Check baud rate
Set next CiA
baud rate
Listen on other
side for x seconds
Set next CiA
baud rate
Check baud rate
Restart timeout
Baud rate found is
used on both sides
CANbridge
switches off
Normal
operation
Bus activity
Restart
CAN
Wrong
baud rate
Baud rate found
on one side
Timeout
expired
Transmission
error
Transmission
successful
Baudrate
found
False
baud rate
Restart
CAN
Bus
activity
Start
Fig. 5-1: Status diagram automatic baudrate detection
Copyright IXXAT Automation GmbH
CANbridge - Manual, V1.4
19