Accessories for cooling station
6 720 642 838
(2010/03)
5
3
Accessories for cooling station
The following accessories are available for control of the
passive cooling system:
•
LK three-way change over valve (E11.Q12) Three-way
change over valve is connected to the XB2 card in the
cooling station. The three-way change over valve can
be used to by-pass the buffer tank to protect it against
cooling. Power supply 230 V.
•
Room transducer for relative humidity and
temperature (E11.TM) (dew point sensor)
Sensor for registering room temperature and
humidity in a reference room. Sauters room
transducer for relative humidity and temperature is
connected to the XB2 card on the cooling station by a
4x2x0.8 mm
2
cable. Power supply 24 V via the
transformer in the cooling station.
•
Electrical distributor for heating/cooling Sauters
electrical distributor for heating/cooling for
underfloor heating loops is connected to the XB2 card
on the cooling station. Room temperature controller,
room transducer for relative humidity and
temperature and actuators are connected to the
distributor. The heat pump's C/O signal (switch from
heating to cooling) is connected to the distributor.
Distributor power supply 230 V. The heat pump's C/O
signal can only be managed from Sauters cable bound
distributor ASV6F116. The remote control controller
from Sauter cannot transfer the signal onwards.
•
Electrical room temperature controller for heating/
cooling 230 V. Sauters room temperature controllers
are connected to the distributor by 7x1.5mm
2
cable.
•
Thermal drive for unit valves Sauters thermal drives
for unit valves are connected to the distributor. Power
supply 230 V.
•
Dew point monitor and transducer Sauters dew point
monitor and transducer and room temperature sensor
are used for comprehensive dew point monitoring
and are connected to the floor distributor flow line by
a tension strap. Dew point monitor and transducers
are connected to the distributor by 7x1.5mm
2
cable.
•
Dew point monitoring The electronic dew point
monitor (E31.RM1) AL-Re can be used to monitor the
dew point, as a complement to the two recommended
components from Sauter. Power supply 24 V via the
transformer in the cooling station. The dew point
monitor is connected to the XB-2 card of the cooling
station by a 2-core cable.
•
Humidity sensor The Humidity sensors (TM1-TM5)
from AL-Re are sensors that are also used for dew
point monitoring and are connected to the electronic
dew point monitor. Maximum of five humidity sensors
can be connected.