Technical information
6 720 642 838 (2010/03)
16
6.4
Technical Data
6.4.1
PKS 1000
Unit
Operation passive cooling station
Cooling output B5/W20
kW
15,5
kW
10,4
Cooling output B15/W20
1)
1) The output details are stated for Bx/W20, which means that temperature of incoming heat transfer fluid is x and the radiator water
return temperature is 20 °C
kW
5,2
Temperature reduction at B10/W20 and water flow 0.38 l/s
°C
6,5
Heat transfer fluid
Nominal flow
l/s
0,42
Permitted ext. pressure drop at heat transfer fluid nominal flow
kPa
32
Max. pressure
bar
4
Operating temperature
°C
-5 - +20
Antifreeze
Ethanol / Propyl-
ene glycol
Highest concentration heat transfer fluid (-15 °C freezing point)
%
29 / 35
Pipe connections
mm
35
Cooling water
Temperature
°C
+15 - +40
Internal pressure drop at water flow 0,38 l/s
kPa
2
Max. pressure
bar
3
Pipe connections
mm
28
Values for electrical connection
Electrical supply
VAC/Hz
230V/1-50Hz
Electrical consumption
kW
0,1
Factory setting circulation pump step 3
W
100
Enclosure class
IP
X1
General
Dimensions (height x depth x width)
mm
500 x 373 x 433
Weight
kg
32
Extra height pipe connections
mm
62
Tab. 9