Settings

6 720 642 838 (2010/03)

30

>> Minimum PID signal

>> Maximum PID signal

>> Mixing valve running time

9.3

Circuit 2, 3...

Under 

Circuit 2

 makes settings for the first shunted 

circuit, E12. Connection board XB1 for this circuit is part 
of the heat pump. Other circuits are displayed only if 
they are connected via accessory IVT mixing valve 
module 1000. The same settings apply to these as for 

Circuit 2

Mixing valve operating mode

B

Set operating mode for the mixing valve according to 
the capacity and current needs of the valve. 

B

For circuit E13 in system solutions ( Page 15) 

Cooling

 must be selected. 

B

For circuit E12 in system solutions  (  Page 13 
and 14) 

Heating/Cooling

 must be selected, if heating/

cooling operation is wanted.

Heat curve

 (in operating mode 

Heating

 and 

Heating/

Cooling

)

> Type of heating system

B

Select type of heating system.

Cooling

The settings are the same as the primary cooling circuit, 
except that 

Acknowledge anti-freeze sensor T32

 and 

Anti-freeze limit T32

 are not displayed. These menus 

apply in general.

Settings for dew point sensor apply to room transducer 
for relative humidity and temperature E12.TM connected 
to the heat pump. Circuit E13 (and E31) does not need 
a room sensor (dew point sensor), the circuits are 
condensation insulated.

Factory setting

0%

Lowest value

0%

Highest value

100%

Tab. 30 Minimum PID signal

Factory setting

100%

Lowest value

0%

Highest value

100%

Tab. 31 Maximum PID signal

Factory setting

300s

Lowest value

1s

Highest value

6000s

Tab. 32 Mixing valve running time

CAUTION: 

Change the value for the mixing 

valve running time to the value specified on 
the mixing valve. If the time is not specified 
on the mixing valve: move the mixing valve 
manually (  Chapter 9.2) and measure how 
long it takes to reach the fully open position 
from the fully closed position (the mixing 
valve audibly closes and the end position 
switch kicks out).

Factory setting

Off

Alternative

Heating

Heating/Cooling

Cooling

Off

Tab. 33 Mixing valve mode

Factory setting

Underfloor

Alternative

Radiator/Underfloor

Tab. 34 Type of heating system

Содержание PKS 1000

Страница 1: ...Installer Guide PKS 1000 6 720 641 553 08 1I Passive Cooling station Art no 6720642838 Version 2010 03...

Страница 2: ...7 Installation 17 7 1 CAN BUS 17 7 2 Handling circuit boards 18 7 3 Assembly 19 7 4 Removing the front panel 19 7 5 Connection 19 7 6 Filling the heating system 21 7 7 Volume flow via the heating syst...

Страница 3: ...y are authorised to do so or are supervised by a person who is responsible for their safety B Supervise children to make sure they do not play with the appliance Service and maintenance B Only qualifi...

Страница 4: ...the delivery 6 720 642 838 2010 03 4 2 Included in the delivery Fig 1 Included in the delivery 1 Passive cooling station 2 Spacer foot 3 Wall mounting 4 Handbook 5 CAN BUS cable 3 5m 6 720 641 553 09...

Страница 5: ...o the distributor Distributor power supply 230 V The heat pump s C O signal can only be managed from Sauters cable bound distributor ASV6F116 The remote control controller from Sauter cannot transfer...

Страница 6: ...Passive cooling station 3 Electrical distributor for heating cooling underfloor heating loop 4 Control distributor 5 Room transducer for relative humidity and temperature dew point sensor 6 Electrica...

Страница 7: ...ature has fallen to the specified value The desired flow temperature is set by the installer The system must be protected from condensation either by the flow line temperature being set sufficiently h...

Страница 8: ...th measurements in mm 1 Roof decal 2 Type plate Fig 5 Height measurements in mm Fig 6 Dimensions in mm 6 720 641 553 01 1I 28 28 35 35 500 500 500 500 373 373 373 373 6 720 615 125 24 1I 6 720 615 125...

Страница 9: ...Dimensions 6 720 642 838 2010 03 9 Fig 7 Roof decal 1 HTF coll in 2 Heat transfer fluid cooling out 3 Heat transfer fluid cooling in 4 HTF coll out 13720 6 720 615125 14 1I 1 2 3 4...

Страница 10: ...838 2010 03 10 6 Technical information 6 1 Component parts Fig 8 Component parts 1 24 V Transformer 2 Terminal block X1 3 Circuit board XB2 4 Mixing valve 5 Heat exchanger 6 Circulation pump 24V 220V...

Страница 11: ...2 E13 E13 G1 Circulation pump E13 G2 Fan assisted radiator E13 Q11 Mixing valve E13 T1 Flow sensor E13 TM Room transducer for relative humid ity and temperature Dew point sen sor E13 TT Room sensor Ta...

Страница 12: ...t monitor E31 RM1 TM1 2 Dew point monitor humidity sensor 1 2 E31 T31 Flow sensor E31 TM Room transducer for relative humidity and temperature Dew point sensor E31 TT Room sensor E31 V101 Filter E41 E...

Страница 13: ...ts have room sensors E11 TT and E12 TT humidity sensors E31 RM1 TM1 and E31 RM1 TM2 and room transducer for relative humidity and temperature E11 TM and E12 TM dew point sensor The humidity sensors ar...

Страница 14: ...nsors E11 TT and E12 TT humidity sensors E31 RM1 TM1 and E31 RM1 TM2 and room transducer for relative humidity and temperature E11 TM and E12 TM dew point sensor The humidity sensors are connected to...

Страница 15: ...ed from circuit E31 via accessory IVT mixing valve module 1000 Both circuits have room sensors E31 TT and E13 TT humidity sensors E31 RM1 TM1 and E31 RM1 TM2 and room transducer for relative humidity...

Страница 16: ...l s 0 42 Permitted ext pressure drop at heat transfer fluid nominal flow kPa 32 Max pressure bar 4 Operating temperature C 5 20 Antifreeze Ethanol Propyl ene glycol Highest concentration heat transfe...

Страница 17: ...ection between the circuit boards is by four wires because the 12V supply between the circuit boards must also be connected The circuit boards have markings for both the 12V and CAN BUS connections Sw...

Страница 18: ...electronics Keep a distance of at least one metre from expanded polystyrene protective plastic and other packaging synthetic material e g fleeces and similar before starting work A condition for good...

Страница 19: ...oom sensor accessory The room sensor is an accessory that must be used in system solutions with cooling Installation location requirements If possible interior wall without drafts or heat radiation Un...

Страница 20: ...e humidity is most likely to form 7 5 4 Three way change over valve accessory System solution Chapter 6 3 1 Chapter 6 3 2 requires a three way change over valve E11 Q12 so that the buffer tank does no...

Страница 21: ...ing installation to between 1 and 2 bar B Check the seal of all joints 7 7 Volume flow via the heating system When a buffer tank is connected in parallel with the heating system no demand is placed on...

Страница 22: ...ed line Accessory TR1 Transformer E31 RM1 Dew point monitor E31 RM1 TM1 5 Humidity sensor max 5 E11 TM Room transducer for relative humidity and temperature dew point sensor E11 TM TM1 Room sensor hum...

Страница 23: ...on pump cooling external E31 G33 Circulation pump ground water E31 T31 Flow sensor E31 TT T35 Room sensor E31 TT P1 LED room sensor F51 Fuse 6 3A F52 Fuse 250mA 1 When circuit board XB2 is last in the...

Страница 24: ...Wiring diagram 6 720 642 838 2010 03 24 8 3 Wiring diagram 3 way valve Fig 24 E11 Q12 Three way valve heating cooling BN Brown BK Black BU Blue 6 720 617 643 09 1I 2 6 3...

Страница 25: ...gram electrical distributor for heating cooling ASV6F116 Electrical distributor for heating cooling from Sauter EGH 102 Room transducer for relative humidity and temperature from Sauter dew point sens...

Страница 26: ...ages all components that are connected to the heat pump and cooling station Accessories connected to the control distributor for underfloor heating are not controlled by the control unit The control d...

Страница 27: ...erature at minimum outdoor temperature Parallel offset Highest permitted flow temperature T1 Lowest permitted flow temperature T1 Cooling mixing valve mode is heating cooling or cooling Allow cooling...

Страница 28: ...the same sensor is used for heating cooling B Select E31 TT if the room sensor connected to the cooling station is to be used E31 TT must be used if only the cooling function is wanted B Select None i...

Страница 29: ...in order to reach the flow set point when there is a need The signal determines how much the opening of the mixing valve should change It is calculated with short time intervals Set default values giv...

Страница 30: ...anti freeze sensor T32 and Anti freeze limit T32 are not displayed These menus apply in general Settings for dew point sensor apply to room transducer for relative humidity and temperature E12 TM con...

Страница 31: ...r circuit pump G3 active in cooling B Do not change the factory setting No Timers Setting Factory setting Level Cooling timers Cooling heating change over delay primary cooling circuit Circuit 1 Cooli...

Страница 32: ...0 0 0 0 100 300s 1 1 1 1 1 1 Circuit 2 3 Mixing valve mode Off 1 Heat curve mixing valve operating mode is Heat ing or Heating Cooling Type of heating system Underfloor 1 Flow temperature at minimum o...

Страница 33: ...talled according to Chapter 6 3 1 and 6 3 2 Room transducer for relative humidity and temperature dew point sensor Chapter 7 5 2 E11 TM E12 TM Dew point monitor with connected humidity sensor Chapter...

Страница 34: ...T10 C Heat transfer fluid coll out T11 C Temperature difference between Heat transfer fluid coll in T10 and Heat transfer fluid coll out T11 approx 2 5 K C Setting heat carrier pump G2 Setting collec...

Страница 35: ...6 720 642 838 2010 03 35 Notes...

Страница 36: ...Ice Energy Unit 2 Oakfield House Oakfield Industrial Estate Eynsham Oxon OX29 4 TH United Kingdom www iceenergy co uk mailroom iceenergy co uk...

Отзывы: