With a disconnected
Device, the “Device
Disconnected” message
does not appear.
Parameter set incorrectly.
Set parameter “
Popup on
disconnected Device
” to
“
Yes
”.
Check Backplane and/or
Extension IQ Easy parameter
“
Device timeout
”. This may not
be set to “
0 seconds
”.
Set to a value like e.g.
“
5 seconds
”.
Device cannot be
switched on or off using
the screen (icons change,
but the Device remains in
the same status).
Device is configured to
respond to the remote on/off
input of the machine
control/PLC.
Change the “
Remote on/off
source
” parameter to
“
Continuous
”.
The IQ Easy system
becomes very slow due
to many Remote On/Off
changes.
Parameter set incorrectly.
Set parameter “
Real-time
screen refresh
” to a value
between 1 and 5 seconds.
As a Basic user, Devices
cannot be put in Run
mode.
Incorrect authorisation setting.
Set parameter “
Standby/Run
access level
” to “
Basic
”.
As an Advanced user,
Devices cannot be put in
Run mode.
Incorrect authorisation setting.
Set parameter “
Standby/Run
access level
” to “
Advanced
”.
With a Global Run, the
Device does not enter
Run mode.
Setting error.
Set the Device parameter
“
Autorun
” to “
On
”.
Unable to log in as an
Advanced user.
Forgot password
Log in as Expert and enter the
Advanced password again. See
Section 6.17.6, parameter
“
Advanced password
”.
It is not possible to log in
as an Expert user.
Forgot password
Reset the Expert password.
See Section 6.17.7. Then enter
the password again. See
Section, 6.17.5, parameter
“
Expert password
”.
After pairing Devices, the
“
Available segments
”
parameter shows “
None
”
instead of the available
segments.
Close the Manager IQ Easy
application and then restart it
(“
Restart
”), see Section 6.16.
After reconnecting
Devices, all Paired
Devices are paired
incorrectly.
Devices connected to other
ports (swapped).
Undo all links between the Paired
Devices (see Section 6.18), close
the Manager IQ Easy application
and restart it (“
Restart
”, see
Section 6.16). Then reset all links
between Paired Devices (see
Section 6.18).
Fieldbus parameters are
not visible.
Missing Anybus module.
Place the correct Anybus module
in the Manager IQ Easy.
Backplane software does not
support the Anybus.
Loads the right Backplane
software for your system.