A1 | HEAT PUMP
Code
Cause
Solution
A1 21
The compressor starting current is too high.
-
Contact your installer or service organisation.
The compressor temperature protection setting is not
functioning properly or is faulty.
-
Contact your installer or service organisation.
A1 22
The phase order in the power socket is not clockwise on
heat pump.
-
Contact your installer or service organisation.
A1 23
There is no clockwise field on the incoming 3 phase power
supply on heat pump.
-
Contact your installer or service organisation.
A1 24
The power consumption of the compressor is too low.
-
Contact your installer or service organisation.
A1 25
The power consumption of the electric heating element is
too low.
-
Contact your installer or service organisation.
A1 26
The power consumption of the compressor is too high.
-
Contact your installer or service organisation.
A1 27
The power consumption of the electric heating element is
too high.
-
Contact your installer or service organisation.
A1 28
The source feed temperature (T8) is too low.
-
Contact your installer or service organisation.
A1 29
The source return temperature (T9) is too low.
-
Contact your installer or service organisation.
A1 30
The liquid temperature (T7) is too high.
-
Contact your installer or service organisation.
A1 31
The discharge temperature (T6) is too high.
-
Contact your installer or service organisation.
A1 32
The injection temperature (T4) is too low.
-
Contact your installer or service organisation.
A1 33
Too high discharge temperature in relation to the liquid
temperature and the expansion valve is completely open.
-
Contact your installer or service organisation.
A1 34
The central heating supply temperature (T10) is too high.
-
Check the water-side flow of the central heating
system.
-
Vent the heating system.
A1 36
Thermostat communication error.
-
Is the room thermostat properly connected?
-
If the appliance remains in an error state or the
same error occurs repeatedly, contact your
installer or service organisation.
A1 37
Compressor power consumption without control.
-
Contact your installer or service organisation.
A1 38
The element relay lingers.
-
Contact your installer or service organisation.
A1 42
Temperature sensor T8 (Source supply) and T9 (Source
return) are not functioning properly or are defective.
-
Contact your installer or service organisation.
A1 43
An unsuitable thermostat is connected.
-
Contact your installer or service organisation.